96
UMG 96RM-M
Table 1 - Parameter list
0
SHORT
RD/WR
-
Device address
0..255
(*1)
1
1
SHORT
RD/WR
kbps
Baud rate (0=300, 1=600, 2=1200,
0..7
5
3= 2400, 4=4800, 5=9600. 6=19200,
7=38400
Baud
3
SHORT
RD/WR
Only for internal use
10
FLOAT
RD/WR
A
Current transformer I1, primary
0..1000000
(*2)
5
12
FLOAT
RD/WR
A
Current transformer I1, sec.
1..5
5
14
FLOAT
RD/WR
V
Voltage transformer V1, prim.
0..1000000
(*2)
400
16
FLOAT
RD/WR
V
Voltage transformer V1, sec.
100, 400
400
18
FLOAT
RD/WR
A
Current transformer I2, primary
0..1000000
(*2)
5
20
FLOAT
RD/WR
A
Current transformer I2, sec.
1..5
5
22
FLOAT
RD/WR
V
Voltage transformer V2, prim
0..1000000
400
Adress
Format
RD/WR
Unit
Note
Adjustment Range Default
Parameter and Modbus address list
The following excerpt from the parameter list contains
settings that are necessary for proper operation of the
UMG 96RM, such as current transformers and device
addresses. The values in the parameter list can be
written and read.
In the excerpt, the measured value list files the measured
and calculated measured values, output status data
and recorded values so that they can be read.
(*1)
The values 0 and 248 to 255 are reserved and must not be used.
(*2)
The adjustable value 0 does not produce any sensible energy values and must not be used.
Summary of Contents for UMG 96 RM-M
Page 13: ...13 UMG 96RM M...
Page 15: ...15 UMG 96RM M...
Page 33: ...33 UMG 96RM M...
Page 81: ...81 UMG 96RM M...
Page 103: ...103 UMG 96RM M Bottom view 97 91 5 Cutout dimensions 92 0 8 92 0 8...
Page 111: ...111 UMG 96RM M...