27
UMG 96RM-M
Total current measurement
If the current measurement takes place via two current
transformers, the total transformer ratio of the current
transformer must be programmed in the UMG 96RM-M.
Example: The current measurement takes place via two
current transformers. Both current transformers have
a transformer ratio of 1000/5 A. The total measurement
is performed with a 5+5/5 A total current transformer.
The UMG 96RM must then be set as follows:
Primary current:
1000 A + 1000 A = 2000 A
Secondary current:
5 A
Fig. Current measurement via a total current transformer
(example).
UMG
S
2
I
S
1
P
1
P
2
Einspeisung 1
Supply 1
Einspeisung 2
Supply 2
1P
1
1P
2
(K)
(L)
(k)
(l)
1S
2
1S
1
1S
1
1S
2
2S
1
2S
2
2S
1
2S
2
(k)
(l)
(K)
(L)
2P
1
2P
2
Verbraucher A
Consumer A
Verbraucher B
Consumer B