17. Configuration of Core Module Settings
17.1 Configuration Methods
The Core Module can be configured in three diffe-
rent ways:
1. Via the USB Interface using a USB Flash Drive
with the Configuration File / spreadsheet. This
is the recommended and most flexible method.
2. Using the onboard Web Console by directly
access the Core Module over an Ethernet con-
nection with a standard HTML browser via IP
access to the monitor using a network or direct
Ethernet connection. This method is current-
ly limited to changing only communications
settings.
3. Writing to Modbus registers using a Modbus
utility
17.1.1 Configuring via the USB Interface using
the spreadsheet application
Open the spreadsheet “Core Module Configura-
tor” using Microsoft Excel. Make sure to select the
spreadsheet tab “FORM”
Follow the instructions on the sheet and make any
required changes to the fields highlighted in color.
Explanations for these fields will be visible when
the cursor hovers over the field.
Light blue fields will have a drop down menu, whi-
le olive and pink colored fields will require a direct
entry. Always view the notes field to find the entry
parameters for directions.
When all data entry is complete, select the red
“CONFIG” tab spreadsheet and save the sheet
as a comma delimited text file (.csv) using the file
name “config”. The resulting file will be saved as
“config.csv”.
Save as “config.csv”
Transfer the file onto a USB flash drive or save
directly to the flash drive. Place the USB flash
drive into the USB port of the Core Module. If the
Core Module is energized it will need to be power
cycled. Once the Core Module is energized wait 20
seconds and the configuration data will automati-
cally be extracted from the .csv file.