UMG 804
www.janitza.com
36
17.1.2 Configuring via the Onboard Web
Console
The onboard web console may be used to config-
ure the serial or Ethernet communications param-
eters but advanced configuration must be done
using the spreadsheet or directly via a Modbus
communications utility. The web console also
gives a real time view of device readings allowing it
to be used for confirmation of proper operation.
1. Connect either Ethernet port of the Core
Module to an accessible network or directly to
the Ethernet port of a PC. Note that some PCs
configured with security features may not per-
mit direct connection of an end user device.
2. Using a standard web browser, enter the IP
address of the Core Module and select the
[Network] tab on the web console. The default
IP address is 192.168.5.77
3. If the web console of the Core Module does not
appear, ping the IP address using the windows
command line prompt “ping_ 192.168.5.77” to
confirm the communications link.
4. When the web console appears click on the
login tab on the top right corner then click on
the green “login” button. Note that there is no
user name or password for the default config-
uration.
Use the default login of “admin” and default
password of “admin”. This may be changed as
required.
Summary of Contents for UMG 804
Page 11: ...www janitza com UMG 804 11...