20
800-DI14 module
www.janitza.de
Bus connector
contacts
DIN rail
Bus connector
sockets
JanBus
Interface
JanBus
interface
for further
modules
End bracket
Bus connector
sockets
Fig. Mounting example:
Front view of UMG 801 (basic device) with 800-DI14 module
INFORMATION
The figure above shows an example of mounting the
800-DI14 module. Use end brackets to set up your
device and module series on the DIN rails.
INFORMATION
After installing your module, check the function of
the communication between the basic device and
the module using the display on the basic device
as
follows:
·When you are in the
Home
measuring display
of
the basic device
, pressing the button 1
ESC
takes
you to the
Menu
window.
·Use buttons 2 (
5
) and 5 (
6
) to select the menu
item
System information
and confirm with button 3
Enter
.
·The
System information
window with the items
Basic device
and
Module 1
appears.
·The basic device has detected module 1.
Observe the following:
·The basic device allows the mounting of
up to 10
modules
!
·Always start and end your device and module se-
ries with end brackets.
Basic device
Module 1
System Information
ESC
Lorem ipsum
Fig. System information window with the en-
tries of the basic device and module 1.
INFORMATION
The basic device does not recognize modules
during the power-up procedure!
If there is no communication to the modules, the mod-
ule functions are not supported (e.g. status messages
of the digital inputs in the
Digital I/O status
menu).
·
Disconnect your system from the power supply
and check the condition of the bus connectors
and the connections of your modules to the ba-
sic device (JanBus interface). If necessary, push
the contacts of the module bus connectors into
the sockets of the basic device bus connector
or the attached modules so that the bus con-
nectors (devices) are coupled.
·
For remote module series, check the connection
of the transfer modules with the connection via
the shield clamps.
·
If necessary, restart the basic device.
·
If these measures do not lead to the desired
result, please contact our Support –
www.janitza.de
Error after starting the basic device with module: