2.5  Electrically qualified personnel

To avoid bodily injury and material damage, only 
electrically qualified personnel are permitted to work 
on the devices and their components, modules, 
assemblies, systems and current circuits who have 
knowledge of:

 ·The national and international accident prevention 

regulations.

 ·Safety technology standards.
 ·Installation, commissioning, operation, disconnec-

tion, grounding and marking of electrical equip-
ment.

 ·the requirements concerning personal protective 

equipment.

Electrically qualified persons within the scope of the 
technical safety information of all usage informa-
tion associated with the device and its components 
(modules) are persons who can furnish proof of 
qualification as an electrically skilled person.

  WARNING

Warning against unauthorized manipulation or 

improper use of the device or its components 

(modules)!

Opening, dismantling or unauthorized manipulation of 

the device and its components (modules) which goes 

beyond the mechanical, electrical or other operating 

limits indicated can lead to material damage or injury, 

up to and including death.

 ·

Only electrically qualified personnel are per-

mitted to work on the devices and their com-

ponents (modules), assemblies, systems and 

current circuits.

 ·

Always use your device or component (module) 

only in the manner described in the associated 

documentation.

 ·

If there is discernible damage, send the device 

or the component (module) back to the manu-

facturer!

2.6  Warranty in the event of damage

Any unauthorized tampering with or use of the 
device, component or module constitutes “misuse” 
and/or “negligence” under the product’s warranty 
and thus voids the warranty for any possible re-
sulting damage. Note in this regard Sect. “3.3 
Intended use” on p. 13.

2.7  Safety information for handling current 

transformers/current sensors

Definition of the terms current transformers/cur-
rent sensors:

In this user manual, the term 

"current transformer"

 

is used for special transformers for the proportional 
conversion of currents of large amperages to directly 
measurable, smaller 

current values

.

In contrast, the term 

"current sensor" 

is used for 

special transformers for the proportional conversion 
of currents of large amperage to directly measurable, 
smaller 

voltage values

.

Current transformers and current sensors provide a 
safe galvanic isolation between the primary circuit 
and the measurement circuit due to their construc-
tive design and their physical operating principle.

  WARNING

Risk of injury due to large currents and high elec-

trical voltage on the current transformers!

Current transformers operated while open on the 

secondary side (high voltage peaks pose a hazard 

when touched) can result in severe bodily injury or 

death.

 ·

Avoid operating the current transformers while 

open; short circuit the unloaded transformers!

 ·

Before interrupting the current supply, short 

circuit the secondary connections of the cur-

rent transformers. Switch any test switches 

that automatically short circuit the secondary 

lines of the current transformers to the “Test” 

status (Check the test switch/short circuiting 

connection beforehand)!

 ·

Only use current transformers/current sensors 

with basic insulation according to IEC 61010-

1:2010!

 ·

Caution, even current transformers rated as 

safe for open operation can pose a hazard 

when touched during operation while open!

 ·

Make sure that screw terminals for the current 

transformer connection on the device are ade-

quately tightened!

 ·

Comply with the information and provisions in 

the documentation of your current transform-

ers!

Summary of Contents for 800-CON

Page 1: ...e Transfer module set of 2 for the UMG 801 User manual and technical data Janitza electronics GmbH Vor dem Polst ck 6 35633 Lahnau Germany Support 49 6441 9642 22 info janitza com www janitza com Doc...

Page 2: ...800 CON Modules www janitza com 2 800 CON transfer module set of 2 for the UMG 801 Doc no 2 053 087 0 a Date 02 2023 The German version is the original edition of the documentation...

Page 3: ...e current state of the information available to us Nonetheless we wish to point out that updates of this document are not always possible at the same time as technical refinements are implemented in o...

Page 4: ...ormation for handling current transformers current sensors 10 3 Product description 12 3 1 800 CON module set of 2 12 3 2 Incoming goods inspection 12 3 3 Intended use 13 3 4 Overview of module functi...

Page 5: ...n function of the meter and module topology 23 7 Device views 800 CON transfer module 24 8 Technical data 25 9 Dismounting 26 10 Service and maintenance 27 10 1 Repair 27 10 2 Service 27 10 3 Device a...

Page 6: ...ion accompanying the product Keep the usage information associated with the product available for the entire service life and pass it on to any possible subsequent users Find out about device revision...

Page 7: ...reight complete with accessories Observe special regulations for devices with built in batteries or rechargeable batteries Do not attempt to open or repair the device the module the component on your...

Page 8: ...tuation which if not avoided can result in material or environmental damage INFORMATION Indicates procedures in which there is no hazard of personal injury or material damage 2 3 Product safety The de...

Page 9: ...er circuits when open Only connect screw terminals with the same number of poles and design Do not exceed the limit values specified in the user manual and on the rating plate This must also be observ...

Page 10: ...nty for any possible re sulting damage Note in this regard Sect 3 3 Intended use on p 13 2 7 Safety information for handling current transformers current sensors Definition of the terms current transf...

Page 11: ...sformers can be hot even after the power supply has been switched off Allow the connections of the current transformers and the connecting cables to cool down before touching them CAUTION Risk of inju...

Page 12: ...le tools Check the modules by performing a visual inspection to ensure flawless mechanical condition the scope of delivery see Sect 3 8 Scope of delivery 800 CON transfer module set of 2 on p 14 for c...

Page 13: ...l data on p 25 3 5 EU conformity declaration Please see the EU declaration of conformity posted at www janitza com for the laws standards and di rectives applied by Janitza electronics GmbH for the de...

Page 14: ...The UMG 800 CON set of 2 expansion and transfer module is used for connecting remote measurement points as previously described in Sect 3 1 800 CON module set of 2 on p 12 The modules can be used to r...

Page 15: ...www janitza com 15 800 CON Modules...

Page 16: ...to Janitza electronics GmbH in accordance with the shipping in structions for air or road freight complete with accessories All usage information is also available as a download at www janitza com 4 1...

Page 17: ...a on p 25 until the 2 bottom bolts engage 800 CT8 A module Fig Side view UMG 801 800 CT8 A and 800 CON module DIN rail 800 CT8 A module Fig Side view UMG 801 800 CT8 A and 800 CON module UMG 801 4 Pus...

Page 18: ...onnectors and the connections of your modules to the basic device JanBus interface If necessary push the contacts of the module bus connectors into the sockets of the basic device bus connector or the...

Page 19: ...odule input bus connector Connector for insertion into the rear of the module 7 Transfer module input bus connector Sockets for module insertion INFORMATION The transfer modules 800 CON of the set of...

Page 20: ...for Danger sign General hazard symbol Be certain to observe the warning notices applied to the device and shown in the documentation in order to avoid possible injury or even death 3 Device type Devic...

Page 21: ...www janitza com 21 800 CON Modules...

Page 22: ...nector from left to right This will avoid an incorrect connection of remote JanBus systems Use end brackets and shield clamps with strain relief to set up your meter and module topology on a suitable...

Page 23: ...e 800 CON transfer modules Recommendation Use the following data cables for smooth com munication in your meter and module topology for connecting the 800 CON transfer modules 1 1 Cable connection INF...

Page 24: ...iew from left Plug for insertion into the basic device or an attached module Bus connector for the output transfer module Sockets for module insertion Bus connector for the input transfer module Conne...

Page 25: ...1 5 mm2 AWG 24 16 Wire ferrules non insulated 0 2 1 5 mm2 AWG 26 16 Wire ferrules insulated 0 2 1 mm2 AWG 26 18 Tightening torque 0 2 0 25 Nm 1 77 2 21 lbf in Strip length 7 mm 0 2756 in General Net...

Page 26: ...ver 1 Disconnect the supply of power to the system Secure it against being switched on Check to be sure it is de energized Ground and short circuit Cover or block off adjacent live parts 2 Disconnect...

Page 27: ...transfer module set of 2 For a firmware update of the further components and modules of your meter and module topology please refer to the respective usage information INFORMATION This user manual des...

Page 28: ...Janitza electronics GmbH Vor dem Polst ck 6 35633 Lahnau Germany Support tel 49 6441 9642 22 Email info janitza com www janitza com...

Reviews: