Operation and Maintenance
Envistar Top 04-21
DSET.220501.07.en
Continuous product development may give rise to specification changes without notice.
5.7 Cooling Status - reversible heat pump (code TTC)
With control equipment (code MX)
Status information is read on the Climatix display.
Information
Value/example
Explanation
Cooling unit status
UnitOn
Normal status for cooling mode if the
compressor is running depends on the
cooling load.
OFFbyALR
Switched off caused by alarm.
OFFbyDIN
Switched off due to interlock. Climatix
interlocks cooling operation.
OFFbyKey
Switched off due to Carel’s ON/OFF
menu.
HighcondTmp
Compressor speed lowered due to the
high pressure is high.
FrostProtOpr
Compressor speed lowered to protect
the evaporator from freezing. This is
not a fault, but a result of extract air
flow and extract air temperature.
Status HP
Alarms
The heat pump is in alarm mode.
OffbyKey
Switched off due to Carel’s ON/OFF
menu.
Temp ctrl.off
The unit is shut off.
Cooling mode
The heat pump is in cooling mode.
Low outdoor temp The heat pump is blocked as the out-
door temperature is too low.
Low air flow
The heat pump is blocked as the air
flow is too low.
Low return air
temp
The heat pump is blocked as the re-
turn air temperature is too low.
HP Tmp dead
The heat pump does not start due to a
small temperature deviation.
Switch off delay
The heat pump is prevented from
switching off due to a short time since
start.
Switch on delay
The heat pump is prevented from star-
ting due to a short time since stop.
Heating mode
The heat pump is in heating mode.
No need
No need to run the compressor in the
heat pump.
Heating
0%
Heating requirement sent from Clima-
tix to Carel.
Cooling
50%
Cooling load sent from Climatix to
Carel.