Page 25
Operation and Maintenance
Envistar Top 04-21
DSET.220501.07.en
Continuous product development may give rise to specification changes without notice.
Without control equipment (code UC, MK or US)
Status information is read on the Carel display (Main menu/Status - I/O).
Information
Value/example
Explanation
Status A01
U6 = Cool.demand:
50%
Cooling load from ventilation control
Remove start delay:
No / Yes
Opportunity to quick start the compressor if Yes is set.
J6 = Modbus Online:
No/Yes
Information about Modbus communication is received.
Modbus command:
Stop/start
Information about command received from Climatix.
Modbus demand:
50%
Information about cooling load received from Climatix.
Status A02
High Press:
25.00 bar
High pressure
Disch.temp:
50.00°C
Hot gas temperature
Low press:
10.00 bar
Low pressure
Suct.temp:
17.00 °C
Suction gas temperature
Status A03
U7 = start/stop
Stop
Input for interlock cooling operation
U10 = Alarm reset
No reset
Input to reset alarm
Status A04
NO6 = General alarm
N/C
Output for sum alarm
Status A05
Overheating
Suction gas temperature
Valve opening
Low pressure
Evaporating temperature