Page 49
Operation and Maintenance
Envistar Top 04-21
DSET.220501.07.en
Continuous product development may give rise to specification changes without notice.
Inspection
WARNING!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
Check that the elements are correctly positioned and that they are not deformed
in any way.
Cleaning
WARNING!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
Vacuum and/or wipe all surfaces with a cloth.
Function
WARNING!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
1. Simulate reduced required output by temporarily lowering the temperature
setting (setpoint), so that all the electric output steps (contactors) switch out.
2. Then sharply increase the setpoint setting and check that the electric output
steps switch in.
3. Restore the temperature setting.
4. Stop the unit. NB: Do not stop operation with the safety switch! All the elec-
tric output steps should switch out (i.e. the contactors in the OFF position).
Stopping the unit may be delayed a few minutes to allow the fans to cool the
heat energy stored in the air heater.
The electric heater is equipped with dual temperature limiters. The one that re-
sets itself automatically should be set to 70°C.
The overheat protection with manual reset interrupts operation when the heater
reaches approx. 120°C and is located on the cover panel on the side of the hea-
ter.
Determine the cause of overheating and take corrective action before
you reset the protection device.
NB: The risk of overheating increases as the air flow through the unit decreases.
The air speed should not be lower than 1.5 m/s.