Section 9, Installing the Distribution Module
International Thermal Research
9-7
Figure 9-7: Connecting two Heating loops.
Do not operate the POLAR™HD Heating Module and Distribution
Module, DM12 (Optional) until coolant is in the POLAR™ HD
Heating Module and Distribution Module and all trapped air has
been bled.
All plumbing lines must be run and secured so as to prevent
damage, chafing and kinking.
9.5 Filling/Purging the heating system
The Distribution module contains two valves with ½”NPT
connections to be used for filling the heating loop. To initially fill
up and bleed the air out of the system, do the following:
1. Connect a hose to the outlet of a diaphragm pump and to the
“fill inlet valve” on the distribution module. Attach a hose to the
inlet of a diaphragm pump and place the hose in a container
filled with a 50/50 mixture of propylene glycol and water (see
Figure 9-8).
2. Connect a hose to the “fill outlet valve” on the distribution
module and place the other end of the hose in the same
container.
WARNING
NOTICE
NOTICE
Summary of Contents for POLAR HD
Page 1: ...POLAR HD Heating Module Installation and Operating Manual Diesel and AC Heating System...
Page 14: ...Section 1 Overview 1 8 POLAR HD Heating Module...
Page 20: ...Section 2 Mounting the POLAR HD Heating Module 2 6 POLAR HD Heating Module...
Page 30: ...Section 4 Installing the Fuel System 4 4 POLAR HD Heating Module...
Page 46: ...Section 7 Plumbing the System 7 6 The POLAR HD Heating Module...
Page 62: ...Section 8 Operating the Heating Module 8 16 The POLAR HD Heating Module...
Page 76: ...Section 9 Installing the Distribution Module 9 14 The POLAR HD Heating Module...