SLS/SLH 10/06
2.3.8 USER LEVEL - SETPOINT KEY
Press the Set key to enter the Setpoint level, which can
be accessed by the user. The parameters that can be set
User parameters
Control mode
Min. Value
Max. Value
Default
Sys #1 ON/OFF
–
OFF
ON
OFF
Sys #2 ON/OFF
–
OFF
ON
OFF
Cooling Setpoint
Inlet
mCS+2
20
10
Outlet
mCS 20 8
Heating Setpoint
Inlet
20
MHS-2
43
Outlet
20 MHS 45
Glycole Setpoint
Inlet
–15
20
10
Outlet
–15 20
8
Proportional Band
Inlet
1
10
5
Neutral Band
Outlet
1
6
2
Language selection
—
ITA
ENG
FRA
GER
SPA
ITA
Recovery
SYS #2 ON/OFF
—
OFF
ON
OFF
SYS #1 ON/OFF
—
OFF
ON
OFF
Recovery
Setpoint
Recovery
30
50
45
Band
Recovery
2
6
4
Where mCS = min. cold limit for the setpoint (see
Service level)
Where MHS = max. heat limit for the setpoint (see
Service level)
When the machine is turned on, every single circuit is
activated through the SYSTEM # ON/OFF parameters
(SET key).
2.3.9 SERVICE LEVEL KEY
Press the “Prog” key (correct password 1234) to access the Service Level:
Parameters
Type
Min. Value
Max. Value
Default
R134A
unit
On/off remote
enabled
Flag
N=NO
Y=YES
N
Cool/heat remote
enabled
Flag
N=NO
Y=YES
N
Press the key ENTER
for default values
Auto restart
After blackout
Flag
N=NO
Y=YES
N
Glycole enabled Flag N=NO Y=YES N
Clock 32 Kbyte
Flag
N=NO
Y=YES
N
Night management
Flag N=NO
Y=YES
N
Night management
Flag N=NO Y=YES Y
DPOFFSET bar 0 8 2
are listed below, together with the limit values and the
default values (standard shop set-up.
At this level you can select the language of opera-tion
(English, Italian, French,German,Spanish)
Pressing the ENTER key initializes the control: all the Manufacturer
Level/Service Level parameters are forced to the default value.