Defrost mangement
SP Start
bar
0
30
2.8
TC Stop
°C
-20
30
10
Charge time
Sec
0
99
20
Start time
Min
0
99
45
Max time
Min
1
10
5
Off reversing
Sec
0
999
0
Tair off (off in heating)
°C
-20
20
-20
Min. Tair (load discharge in heating)
°C
-20
20
-10
Insert the new service password
1234
Parameters
Type
Min. Value
Max. Value
Default
R134A
unit
Note 2:
Set this parameter to
FSC only if the speed controller is available,
otherwise set it to
STEP.
SETTING OF EEV, EX7 or EX8 type, for YSLS R134a
SERVICE LEVEL 1234
GO INTO THE SERVICE LEVEL (PROG + 1234)
SCROLL THE MASKS DOWN TO THE NEXT
M_PASS_DRIVER
m_manuf_drv1_1
m_manuf_drv1_2
Note:
This is the ratio between the max. cooling capacity of the refrigerant circuit controlled by the valve and the max.
cooling capacity of the valve at 100% opening EX8 with R134A range fron 70 to 680 kW.
1234
U :
Insert password
driver.................... 0000
Parameters
D:1 U:
Valve type
ALCO EX7 o EX8
Parameters
D:1 U:
Percentage ratio
circuit/EEV................40%