2.3.2 ALARMS
Code
Alarm description
Comp 1
Comp 2
Ventil. #1 Ventil. #2 Pump Aut/Man
Delay Notes
Status
Status
Status
Status
Status
Reset
AL00
Automatic alarm intervention
Run
Run
Run
Run
Run
Aut
NO
AL01
Wrong power supply
Off
Off
Off
Off
Off
Man
NO
Phase monitor (1)
AL02
Antifreeze alarm
Off
Off
Off
Off
Run
Man
NO
AL03
Interlock
Off
Off
Off
Off
Off
Man
NO
AL04
Flow meter alarm
Off
Off
Off
Off
Off
Man
NO
AL05
Sys #1 Low pressure - suction
Off
Run
Off
Run
Run
Man
1Time auto
AL06
Sys #2 Low pressure - suction
Run
Off
Run
Off
Run
Man
1Time auto
AL07
Sys #1 High pressure - delivery
Off
Run
Off
Run
Run
Man
NO
AL08
Sys #2 High pressure - delivery
Run
Off
Run
Off
Run
Man
NO
AL09
Thermal switch, compressor 1
Off
Run
Off
Run
Run
Man
NO
AL10
Thermal switch, compressor 2
Run
Off
Run
Off
Run
Man
NO
AL11
Recovery antifreeze alarm
Run
Run
Run
Run
Run
Man
NO
AL12
Sys 1 Fans' thermal switch - unit 1 Run
Run
Off gr.#1 Run
Run
Man
NO
AL13
Sys 1 Fans' thermal switch - unit 2 Run
Run
Off gr.#2 Run
Run
Man
NO
AL14
Sys 2 Fans' thermal switch - unit 1 Run
Run
Run
Off gr.#1 Run
Man
NO
AL15
Sys 2 Fans' thermal switch - unit 2 Run
Run
Run
Off gr.#2 Run
Man
NO
AL16
Sys #1 pressure diff. compressor
Off
Run
Off
Run
Run
Man
NO
AL17
Sys #2 pressure diff. compressor
Run
Off
Run
Off
Run
Man
NO
AL18
Failure of clock card
Run
Run
Run
Run
Run
Man
NO
AL19
AL21
B1-Tin Sensor failure
Off
Off
Off
Off
Run
Aut
NO
note (3)
AL22
B2-LP1 Sensor failure
Off
Run
Run
Run
Run
Aut
NO
note (3)
AL23
B3-DP1 Sensor failure
Run
Run
Run
Run
Run
Aut
NO
note (3)
AL24
B4-Tair Sensor failure
Run
Run
Run
Run
Run
Aut
NO
note (3)
AL25
B5-Tout Sensor failure
Off
Off
Off
Off
Run
Aut
NO
note (3)
AL26
B6-LP2 Sensor failure
Run
Off
Run
Run
Run
Aut
NO
note (3)
AL27
7-DP2 Sensor failure
Run
Run
Run
Run
Run
Aut
NO
note (3)
AL28
B8-Tplan Sensor failure
Off
Off
Off
Off
Run
Aut
NO
note (3)
AL29
B9-Trin Sensor failure
Run
Run
Run
Run
Run
Aut
NO
note (2) (3)
AL30
B10-Trout Sensor failure
Run
Run
Run
Run
Run
Aut
NO
note (2) (3)
AL31
Sys #1 compress. maintenance
Run
Run
Run
Run
Run
Aut
NO
AL32
Sys #2 compress. maintenance
Run
Run
Run
Run
Run
Aut
NO
AL33
Pump maintenance
Off
Off
Off
Off
Off
Man
NO
--------
Eprom failure
Off
Off
Off
Off
Off
Man
NO
AL36
Sys #1 Low pressure - suction
Off
Run
Off
Run
Run
Man
1Time auto
AL37
Sys #2 Low pressure - suction
Run
Off
Run
Off
Run
Man
1Time auto
Note:
1:
check the direction of rotation for power supply and/or minimum voltage phases. Activated only if the Phase Monitor is
provided
2:
forced return from the recovery mode. Recovery mode disabled.
3:
unit alarm on the display “Failure of Sensor No. #”.
Summary of Contents for SLS-SLH