12
SLS-SLH 10/06
m_manuf_drv2_1
m_manuf_drv2_2
m_manuf_d1_ch1
m_manuf_d2_ch1
leave the value at 0, only if the circuit come unstable go to 1.0 °C but
absolutely not over > 1°C
Parametri
D:2 U:
Tipo valvola
ALCO EX7 o EX8
Presenza batteria.........S
Parametri
D:2 U:
Rapporto percentuale
circuito/EEV.............40%
Parameters-CH : D:1 U:
SHeat setp
: 06.0°C
SH Dead band : .0.0°C
Parametri-CH
: D:2 U:
SHeat setp
: 06.0°C
SH Banda morta : .0.0°C
m_manuf_d1_ch2
m_manuf_d2_ch2
m_manuf_d1_ch3
increase this value if the SH is not controlled
15sec with plate heat exchanger
normal range between 2 & 4 °C
normal range between 1 & 10. If 0 the protection must be unable
Parameters-CH
D:1 U:
Prop. gain ........ 050
Int. time ............ 030s
Deriv time ......... 002s
Parameters-CH
D:2 U:
Prop. gain ........ 050
Int. time ............ 030s
Deriv time ......... 002s
Parameters-CH
D:1 U:
SH protection low
SH low ............ 03.0°C
Int. time ............ 002s
IF THE CONTROL PANEL IS SHOWING A LOW PRESSURE ALARM FOLLOW THE NEXT PROCEDURE ...
increase this value if the SH is not controlled
15sec with plate heat exchanger