LIST OF ITELCO-CLIMA APPLICATION SUPERVISOR
VARIABLES FOR PCO2 APPLICATION CHILLER tyìe RLS or SLS or SLH
Level: 1=User (Site manager); 2=Service Manager; 3=Manufacturer; n.c.=not care
Valid for software from release CWFLICIICH0A 1.306 27 May 2003
Index
Meaning
Read/Write
Level
Range
1
Water inlet temperature (RWT)
Read
2
-50.0 ÷ +105.0 °C
2
Water outlet temperature (LWT)
Read
2
-50.0 ÷ +105.0 °C
4
External air temperature (OAT)
Read
1
-50.0 ÷ +105.0 °C
5
System #1 low pressure transducer
Read
2
0.0 ÷ 30.0 bar
6
System #2 low pressure transducer
Read
2
0.0 ÷ 30.0 bar
7
System #1 high pressure transducer
Read
2
0.0 ÷ 30.0 bar
8
System #2 high pressure transducer
Read
2
0.0 ÷ 30.0 bar
9
System #1 defrost temp.
Read
2
-50.0 ÷ +105.0 °C
10
System #2 defrost temp.
Read
2
-50.0 ÷ +105.0 °C
11
Regulated temperature (RWT or LWT)
Read
1
-50.0 ÷ +105.0 °C
12
Sys 1 Fan speed index
Read
2
0.0 ÷ 10.0
13
Sys 2 Fan speed index
Read
2
0.0 ÷ 10.0
24
Discharge pressure setpoint
Read/Write
2
10.0 ÷ 24.0 bar
26
Max fan speed
Read/Write
2
0.0 ÷ 10.0 Vdc
27
Maximum Discharge pressure
Read/Write
2
10.0 ÷ 28.0 bar
28
Discharge pressure limit
Read/Write
2
18.0 ÷ 28.0 bar
35
Antifreeze setpoint
Read/Write
3
-15.0 ÷ +10.0 °C
59
RWT cooling setpoint
Read/Write
1
8.0 ÷ 20.0 °C
60
LWT cooling setpoint
Read/Write
1
6.0 ÷ 20.0 °C
61
RWT glycol cool setpoint
Read/Write
1
-15.0 ÷ 20.0 °C
62
LWT glycol cool setpoint
Read/Write
1
-15.0 ÷ 20.0 °C
63
Neutral zone
Read/Write
2
1.0 ÷ 6.0 °C
64
Proportional Band
Read/Write
2
1.0 ÷ 10.0 °C
84
RWT heating setpoint
Read/Write
1
20.0 ÷ 48.0 °C
85
LWT heating setpoint
Read/Write
1
20.0 ÷ 50.0 °C