iSMA-B-MINI/MIX Modbus User Manual
www.ismacontrolli.com
DMP262en | 1st Issue rev. 8 | 05/2022
page 40 of 107
Register Value
Description
25
NI1000 32F (ºF)
26
NI1000 70F (ºF)
+128
(set 7. bit of register)
Off voltage measurement
Table 15. UI configuration
7.1.6 Filter Time Constant of the Universal Input 1-8 (40159-40166)
These 16-bit registers contain a time constant low pass filter. The value is expressed in
seconds. Valid values must be between 0 and 60 seconds. The default filter value is 2
seconds. Setting the value to 0 disables the filter.
In case of the UI shortcut or open-loop, the filter is reset and the UI value filtering is
stopped.
7.1.7 Resolution of the Universal Inputs (40167)
This register is used to determine the bit resolution for each of the universal inputs.
Setting the bit to 0 sets the resolution of the converter to 12-bit. Setting the bit to 1 sets
the resolution of the converter to 16-bit.
Each input can be configured separately in accordance with the following table:
No. of Bit in Register
No. of Universal Input
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
Table 16. Universal inputs resolution for MIX38 and MIX38-IP
WARNING!
Setting 16-bit resolution increases the measurement time of one channel from 10 ms
to 140 ms. The total time taken to measure all the channels increases from 50 ms to
700 ms.