7.3.4 Default State of 1-6 Analog Outputs (40145-40150)
These 16-bit registers contain the values of voltage in mV, which appear on the analog
outputs after turning the power on or resetting the watchdog.
7.3.5 Configuration Mode of 1-6 Analog Outputs (40168-40173)
These 16-bit registers contain information about the mode of the analog outputs
according to the following table:
Register Value
Description
0 (default)
Voltage output 0-10 V
1
PWM 1Hz
2
PWM 10Hz
3
PWM 100Hz
4
PWM 0.1Hz
5
PWM 0.01Hz
Table 21. AO type settings
7.3.6 Hand Control Status of Analog Outputs (30015)
This register is available only for modules with the manual control of analog outputs.
No. of Bit in Register
Description
0, 1
Hand status of outputs 1
2, 3
Hand status of outputs 2
4, 5
Hand status of outputs 3
6, 7
Hand status of outputs 4
Table 22. AO hand status bits
Value of the Hand Status
Status Description
0
AUTO
1
HAND CONTROL
Table 23. AO hand status value
The current value of the output in the hand mode determines registers from 30125 to
30128.
7.3.7 Hand Control Value of 1-4 Analog Outputs (30125-30128)
The registers contain a percentage value of the manual control for outputs from 1 to 4.