7.3 Analog Output Registers
7.3.1 State of Analog Outputs Operating as Digital Outputs (40019)
Setting a true value of a particular bit of this 16-bit register causes setting the maximum
output voltage (10 V) on the corresponding output and setting the corresponding register
with analog output value (40121-40126) to 0.
Bits of the register correspond to the following analog outputs.
No. of Bit in the Register
No. of Analog Output
0
1
1
2
2
3
3
4
4
5
5
6
Table 19. AO operating as DO for MIX38 and MIX38-IP
7.3.2 Value of 1-6 Analog Outputs (40121-40126)
These 16-bit registers contain the value of analog output voltage in mV.
7.3.3 Default State of the Analog Outputs (Digital) (40144)
Setting a true value of a particular bit of this 16-bits register sets the maximum voltage
(10 V) on the corresponding analog output after turning the power on or resetting the
watchdog.
Bits of the register correspond to the following analog outputs:
No. of Bit in the Register
No. of Analog Output
0
1
1
2
2
3
3
4
4
5
5
6
Table 20. Default state of AO operating as DO form MIX38 and MIX38-IP