iSMA-B-MINI/MIX Modbus User Manual
www.ismacontrolli.com
DMP262en | 1st Issue rev. 8 | 05/2022
page 30 of 107
•
•
5.4.2 Analog Output Relay Connection
Figure 33. An analog output relay connection
5.4.3 Analog Output Actuator Connection
Figure 34. An analog output actuator connection
5.5 Digital Outputs
Digital outputs operate as relay outputs with maximum loads of:
resistive load: 3 A at 230 V AC, and 3 A at 30 V DC;
inductive load: 75 VA for 230 V AC and 30 W for 24 V DC.