Figure 51. The IP configuration page
This page allows for setting parameters such as:
IP Address (read/write): the IP address of the
controller’s
Ethernet interface;
Mask (read/write): the network mask;
Gateway (read/write): the network default gateway;
Http Port (read/write): the http port;
Mac Address (read-only): the Ethernet interface MAC address;
Protocol Type (read-only): the DIP switch protocol selection;
Modbus TCP Port (read/write): the Modbus TCP port number, default 502;
Modbus Address (read-only): the Modbus device address set by rotary switches;
Modbus TCP Communication Timeout (read/write): the timeout value for TCP/IP
messages;
RS485 Timeout (read/write): the timeout value for Modbus RTU/ASCII messages,
Send Modbus Errors (read-only), enable/disable sending Modbus error messages;
BACnet ID (read/write): BACnet ID set by rotary switches, this value can be overridden
by the user; once overridden by the user, changing rotary switches will not affect the
BACnet ID;
BACnet UDP port (read/write): the BACnet IP port.
8.6 Device Management
This page allows for changing the password and rebooting the device remotely.
WARNING!
To save changes, please first click the
“Submit”
button, and then the
“Reboot”
button.