iSMA-B-MINI/MIX Modbus User Manual
www.ismacontrolli.com
DMP262en | 1st Issue rev. 8 | 05/2022
page 67 of 107
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
40123
122
0x7A
VALUE OF ANALOG
OUTPUT 3
Read/write
40124
123
0x7B
VALUE OF ANALOG
OUTPUT 4
Read/write
40125
124
0x7C
VALUE OF ANALOG
OUTPUT 5
Read/write
40126
125
0x7D
VALUE OF ANALOG
OUTPUT 6
Read/write
30125
124
0x7C
HAND STATUS
VALUE 1
Read-only
The current value of analog
output in the hand mode for
MINI with AO
30126
125
0x7D
HAND STATUS
VALUE 2
Read-only
30127
126
0x7E
HAND STATUS
VALUE 3
Read-only
30128
127
0x7F
HAND STATUS
VALUE 4
Read-only
30130
129
0x81
HARDWARE_VERSIO
N
Read-only
The current hardware
version of a device
30131
130
0x82
MAC_ADDRESS (32 –
bits)
Read-only
The MAC address of a
device
40136
135
0x87
BAUD RATE
Read/write
Memory
Transmission speed
The value is considered only
when sections 1, 2, and 3 of
S3 switch are in the OFF
position
The default value is 7680
(76800 bps)
40137
136
0x88
STOP BITS
Read/write
Memory
Supported values are 1 and
2
The default value is 1
40138
137
0x89
DATA BITS
Read/write
Memory
Supported values are 7 and
8
The default value is 8
40139
138
0x8A
PARITY BIT
Read/write
Memory
Parity Bit (40139) The
default value is 0 (no parity)
Allowed values: