background image

Page 

14

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Troubleshooting Guide 

 

If the Utility Controller fails to energize, follow these procedures: 

 

 

 

Verify that the Controller has correct line voltage connected. With the control switch in the 

ON

 

position, the PLC “PWR” light should be illuminated. If it is not, check the wiring connections. 
Remove the wiring junction-box cover and examine wiring connections. 

 

Verify that Touchscreen turns on and initializes. 

 

Touchscreen should start-up on the Home Screen.(Refer to Users Guide)   

 

Verify that PLC Mode switch is set to “RUN” position. 

 

Verify that the Door Panel plug is securely connected to the door terminal. 

 

Check the wiring terminals on the door panel to verify that none has become damaged or disconnected 
during installation. Reconnect, if necessary. 
 

If services do not turn on with switches: 

1.

 

Verify that PLC Mode switch is set to “RUN” position.  

2.

 

Verify proper voltage at corresponding posts on Terminal 2. 

3.

 

If you do not read the correct voltage at the terminal posts, contact an 

ISIMET

 Service 

Representative. 

4.

 

If you read the correct voltage, test the remote relay and/or solenoids to verify that they are 
operational. 

 

In many cases, failure of the system is the result of improper connection of a remote service or device such 
as a remote relay, solenoid or building alarm system. Refer to 

Equipment Specifications

 to confirm that 

correct connections to these services and devices have been made. 
 

Notes:

 

 

Damage to the Electronic Controller and other components can occur from improperly connecting the 
services, overloading the output circuits, or failing to follow all start-up tests and checklists. 

 

In ALL cases, if the system fails or you have questions about the equipment, contact an 

ISIMET

 

Service Representative. 

 

If the results of all test procedures are positive but utilities will not activate,

 

ISIMET

 

recommends that 

you examine and test the various utility services controlled by the unit to verify that they are 
operational and active. 

 

 

If utilities or controlled devices remain operational after the service switch is disengaged, check for the 
following before placing the unit into full operation: 

 

A defect in the remote relay or solenoid 

 

Tampering 

 

The remote relay unit has a control switch with a manual operation position and the switch is in the 
manual position. 
If utilities or devices continue to be active or if you have a question about the operation of the unit, 
contact an 

ISIMET

 

Service Representative immediately.

 

 

Summary of Contents for RLA Series

Page 1: ...3 Residential Water Leak Detection RLA 3 Installation Maintenance Operations and Start up Instructions Read all instructions BEFORE installation and USE of Controller KEEP INSTRUCTIONS FOR FUTURE USE...

Page 2: ...d monitoring systems The system should be thoroughly tested and adjustments made at time of initial operation Periodic testing should be conducted by the user to assure that all components function an...

Page 3: ...nnecting Controlled Services 10 Battery Backup 10 Connecting Alarm Monitoring Wiring 11 Start Up Checklist 11 Start Up Test Preliminary Information 11 Start Up Test 12 Equipment Operation 13 Troublesh...

Page 4: ...be confirmed prior to installation Enclosed with this Manual is a separate registration form The front of the form is for equipment warranty registration The back is a copy of the equipment start up c...

Page 5: ...Page 5...

Page 6: ...n time to ensure that this occurs A Flush Mounting Trim Flange is provided with each flush mounted unit Separate installation instructions and hardware are included with this flange Semi and Flush Tri...

Page 7: ...e followed when connecting the conduit to the service panel Figure 4 Controller Knock out holes Wiring the RLA Controller Important Verify that the electrical supply is disconnected prior to connectin...

Page 8: ...extend lock position STEP 4 Installing Flush Door Trim Figure 7 Prior to installing Door Trim ensure that wall finishes are complete and that the door panel has been installed To install the Flush Doo...

Page 9: ...escription of Status When Light is On PWR PLC has 24VDC from Power Supply RUN PLC is set to RUN Mode and is operational ERR PLC Processor has incurred an error X1 Door Panic Button is being pressed X2...

Page 10: ...ctly to the Output Terminal in order to function as intended Connect Supply Solenoid to the ON w Latch Terminals Make connections to BLK and WHT pins to match instructions provided with the solenoids...

Page 11: ...ct short or input voltage at the output circuit will cause damage to the PLC and Controller Verify that the Door Panel plug is firmly secured to its terminal and ground wire is connected Examine Door...

Page 12: ...ing system a Press and release the red Panic Button b Verify that all Solenoids have been deactivated 2 Press the Reset System button on the screen NOTE Electrical Service will not shut down with Pani...

Page 13: ...l breakage in piping or circuits may cause damage to the facility Integral time delay programming insures that brief seismic or similar activity will not affect services To Activate One or More of the...

Page 14: ...l In many cases failure of the system is the result of improper connection of a remote service or device such as a remote relay solenoid or building alarm system Refer to Equipment Specifications to c...

Page 15: ...all moisture is removed from the compartment The electronic controller PLC is sensitive to moisture dust debris and other air borne particles Do not expose the interior compartment of the enclosure Du...

Page 16: ...not specifically intended for use in applications where a master shut down and re instate device is located away from areas of normal use ISIMET s opinion is that in such cases there is risk that the...

Reviews: