background image

Page 

11

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Connecting Alarm Wiring

   

Alarm Input 

 

The unit will not operate properly without an “Alarm” input signal. 

 

Providing an input signal from the Alarm System at Terminal 1 will notify the RLA Controller if the 
residence is occupied or not.  

Start-Up Checklist:   

 A separate Start-Up Test Sheet is provided with the installation CD.   The tests described herein 
and in those procedures should be followed prior to placing the unit into operation.  If you do not 
have on hand this CD and/or Start-up sheet, you may retrieve a copy from your local factory 
representative. 

 

Caution! 

 

Verify that ALL installation procedures and Line Voltage, Solenoids, and/or Remote Relays 
conform to Equipment Specifications. 

□ 

Examine electrical wiring at junction box to verify that ALL wiring is correctly connected. 

□ 

Examine 

Terminal 1 

and

 Terminal 2

 to assure that wiring has been properly connected. 

Test Output circuits at 

Terminal 2

 to verify that field wiring or connected devices are wired 

correctly.  A direct short or input voltage at the output circuit will cause damage to the PLC and 
Controller. 

□ 

Verify that the Door Panel plug is firmly secured to its terminal and ground wire is connected. 

□ 

Examine Door Panel factory wiring to ensure that it was not damaged or loosened during shipping 

 

or installation. 

□ 

For Building Alarm System, verify that wiring connections, voltage requirements and alarm system 
conform to unit specifications. 

□ 

Remove all dust and construction debris prior to proceeding. 

 

Start Up Test Preliminary Information 

 

Caution! 

 

Do not proceed with equipment start-up until the Start-Up Checklist has been completed

 

Before commencing these Start-Up tests, turn the control switch to the 

OFF

 position. 

 
This unit was factory tested, but the manufacturer recommends that the installer perform these tests to 
ensure that the unit did not sustain damage during shipment or installation.  

      Perform Start-Up Tests with the Door Panel open. 

      With the control switch 

ON

, “PWR” LED on the PLC should illuminate.  If not, check circuitry  

        for 24VDC  power at Power Supply.   

      If after performing these tests and verifying operation, if the Unit fails to function contact an

 

 

ISIMET 

factory representative. 

 

 

Summary of Contents for RLA Series

Page 1: ...3 Residential Water Leak Detection RLA 3 Installation Maintenance Operations and Start up Instructions Read all instructions BEFORE installation and USE of Controller KEEP INSTRUCTIONS FOR FUTURE USE...

Page 2: ...d monitoring systems The system should be thoroughly tested and adjustments made at time of initial operation Periodic testing should be conducted by the user to assure that all components function an...

Page 3: ...nnecting Controlled Services 10 Battery Backup 10 Connecting Alarm Monitoring Wiring 11 Start Up Checklist 11 Start Up Test Preliminary Information 11 Start Up Test 12 Equipment Operation 13 Troublesh...

Page 4: ...be confirmed prior to installation Enclosed with this Manual is a separate registration form The front of the form is for equipment warranty registration The back is a copy of the equipment start up c...

Page 5: ...Page 5...

Page 6: ...n time to ensure that this occurs A Flush Mounting Trim Flange is provided with each flush mounted unit Separate installation instructions and hardware are included with this flange Semi and Flush Tri...

Page 7: ...e followed when connecting the conduit to the service panel Figure 4 Controller Knock out holes Wiring the RLA Controller Important Verify that the electrical supply is disconnected prior to connectin...

Page 8: ...extend lock position STEP 4 Installing Flush Door Trim Figure 7 Prior to installing Door Trim ensure that wall finishes are complete and that the door panel has been installed To install the Flush Doo...

Page 9: ...escription of Status When Light is On PWR PLC has 24VDC from Power Supply RUN PLC is set to RUN Mode and is operational ERR PLC Processor has incurred an error X1 Door Panic Button is being pressed X2...

Page 10: ...ctly to the Output Terminal in order to function as intended Connect Supply Solenoid to the ON w Latch Terminals Make connections to BLK and WHT pins to match instructions provided with the solenoids...

Page 11: ...ct short or input voltage at the output circuit will cause damage to the PLC and Controller Verify that the Door Panel plug is firmly secured to its terminal and ground wire is connected Examine Door...

Page 12: ...ing system a Press and release the red Panic Button b Verify that all Solenoids have been deactivated 2 Press the Reset System button on the screen NOTE Electrical Service will not shut down with Pani...

Page 13: ...l breakage in piping or circuits may cause damage to the facility Integral time delay programming insures that brief seismic or similar activity will not affect services To Activate One or More of the...

Page 14: ...l In many cases failure of the system is the result of improper connection of a remote service or device such as a remote relay solenoid or building alarm system Refer to Equipment Specifications to c...

Page 15: ...all moisture is removed from the compartment The electronic controller PLC is sensitive to moisture dust debris and other air borne particles Do not expose the interior compartment of the enclosure Du...

Page 16: ...not specifically intended for use in applications where a master shut down and re instate device is located away from areas of normal use ISIMET s opinion is that in such cases there is risk that the...

Reviews: