background image

32

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

SYMPTOM

PROBABLE CAUSE

CORRECTIVE ACTION

Thin black coating (soot) 

forms on the viewing 

glass, logs, or firebox

Improper log or ember 

placement

Improper air shutter 

setting

Not enough combus-

tion air

See 

Firebox Liner Kit, Log Set Installation, and Glass Media Installation on Pages 

17 through 19

. If there is soot in one specific location, the glowing embers (rockwool) 

below this location needs to be adjusted. This can be done by pulling embers forward 

slightly. If the flames have soot tails, the shutter will need to be opened.

If sooting continues open air shutter (see 

Air Shutter Adjustment on Page 21).

Check for debris obstructing air flow in valve compartment under insert or in front of 

lower venting.

Humming or whistling 

coming from insert.

Normal operating noise

Obstructed orifice 

opening

See 

Quiet Operation on Page 26

. The noise may be reduced by slightly turning down the 

flame. Turning the flame down will reduce the heat output of the appliance.

If noise is excessive or is “whistling” have your gas supplier check the regulator and 

orifices and replace if necessary.

A change in flame appear-

ance or burner operation.

A change in gas pres-

sure

Improper ember place-

ment

Have your gas supplier check for correct inlet gas supply pressure (7" W.C. / po. C.E. 

[1.74 kPa] natural gas; 11" W.C. / po. C.E. [2.74 kPa] LP gas). 

NOTE:  NEVER BLOCK OR 

OBSTRUCT AIR INTAKE OR OUTLET VENTS.

See 

Firebox Liner Kit, Log Set Installation, and Glass Media Installation on Page 17 

through 20.

The main Burner comes 

on but then goes out.

Gas is not reaching the 

appliance.

Loose wires to the valve 

or ignition module.

Pilot flame is not engulf-

ing the sensor.

Obstructed vent system.

Check the gas supply and gas shutoff valves.

Check control compartment for any obvious loose wiring (call a service technician if required).

Call for a service technician.

Call for a service technician.

Nothing happens when 

the appliance is turned 

On/Off.

Gas is not reaching the 

appliance.

Appliance is not receiv-

ing power.

Check the gas supply and gas shutoff valves.

Check/replace back-up batteries 

(see Battery Backup on Page 21)

.

Check building circuit breakers to ensure power is on to the appliance.

Check Main Power switch on control panel.

The main burner does 

not light and the igniter is 

sparking.

Gas is not reaching the  

appliance.

Loose wires to the 

valve.

Loose wires to ignition 

module.

Air in the gas line.

Check the gas supply and gas shutoff valves.

Check control compartment for any obvious loose wiring (call a service technician if required).

Check control compartment for any obvious loose wiring (call a service technician if required).

Purge gas line of air (call a service technician if required).

The Room Air Blower 

does not turn on with the 

main Burner.

Remote is in Thermostat 

or Smart Thermostat 

mode.

None - blower will turn on after five minute time delay.

TROUBLESHOOTING

NOTE:  When troubleshooting the gas control system, be sure the external gas shut off valve, located at the gas supply inlet is in 

the “ON” position.

IMPORTANT:  Call your gas supplier or plumber for additional help with any gas control problem.  Valve system troubleshooting 

should only be accomplished by a qualified service technician.

Summary of Contents for Madison Park MPI27

Page 1: ...If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage AVERTISSEMENT RISQUED INDENDIE OU D EXPLOSION Le non respect Des avertissements de sécurité pour rait ...

Page 2: ...ALIENTE CAUSARÁ QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO L écran pare étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques incluse avec le façade Requis Unabarrera diseñadaparareducirelriesgodequemadurasdesdelamir...

Page 3: ... en funcionamiento Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros líquidos inflamables alejados de la chimenea Aún después de haber apagado el gas las superficies de la chimenea permanecen extremadamente calientes Asegúrese de colocar las Etiquetas de advertencia de s...

Page 4: ...List 12 Ratings 12 Insert and Fireplace Dimensions 13 Clearances to Combustibles 14 Insert Leveling 14 Installation 15 20 USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Please pay special attention to the safety instructions provided in this manual PRODUCT IS SUBJECT TO CHANGE WITHOUT NOTICE Venting Installation 15 Preparation For Flex Liner Install...

Page 5: ...ls viennent en contact avec la surface chaude Il est recommandé d installer une barrière physique si des personnes à risques habitent la maison Pour empêcher l accès à un foyer ou à un poêle installez une barrière de sécurité cette mesure empêchera les tout petits les jeunes enfants et toute autre personne à risque d avoir accès à la pièce et aux surfaces chaudes 7 Tout écran ou protecteur retiré ...

Page 6: ...ra quitarelpolvoyaceite Peguelaetiquetaadyacente alinterruptordecontroldelquemadorquecontrola elartefacto FiguraA Seleccioneelidiomaquemás se habla en la casa 2 Identifique el transmisor de control remoto y límpielo bien para quitar el polvo y aceite Pegue la etiqueta en la superficie del transmisor Figura B Seleccione el idioma que más se habla en la casa 3 Si no puede encontrar las etiquetas sír...

Page 7: ... étiquettesurleboîtier de la télécommande Figure B Choisissez la langue qui est principalement parlée dans la résidence du propriétaire En cas de doute collez l étiquette en anglais 3 Sivousneparvenezpasàlocaliserlesétiquettes s il vous plaît contactez IHP ou votre revendeur le plus proche pour recevoir IHP étiquettes d instructions de sécurité supplémentaires gratuitement Étiquettes de remplaceme...

Page 8: ...with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance Si l écran est endommagé il doit être remplacé par celui fournit par le...

Page 9: ...er use solid fuels such as wood paper cardboard coal or any flammable liquids etc in this appliance Plated surfaces must be cleaned with glass cleaner and a clean soft cloth before firing the first time or fingerprints will remain permanently NEVER use brass polish to clean plated surfaces this will remove the plating CAUTION Hot while in operation Do not touch Severe Burns mayresult Keepchildren ...

Page 10: ...ed for use with either natural gas or propane Is NOT for use with solid fuels Is approved for sitting rooms and or bedrooms This appliance is suitable for installation into masonry or factory built fireplaces Fireplace Requirements These heaters are designed to be installed into an existing masonry fireplace built to UBC 37 or ULC S628 standards or factory built solid fuel wood burning fireplace l...

Page 11: ...be tested and certified by a nationally recognized testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified to ANSI Z21 88 CSA 2 33 Standard for Vented Gas Fireplace Heater and CAN CGA 2 17 M91 and UL 307B Gas Burning Heating Appliances for Manufactured Mobile Homes in both USA and Canada This appl...

Page 12: ... details PRE INSTALLATION RATINGS MPI27 and MPI27CD NATURAL GAS LP GAS Max Min Input BTUh 0 2 000 Feet 0 610 M u 30 000 21 000 25 000 20 000 Manifold Pressure IN WC 3 5 10 0 Min Inlet Pressure IN WC 5 0 10 5 AFUE Efficiency MPI27 67 MPI27CD 67 MPI27 70 MPI27CD 69 P4 Efficiency v MPI27 68 MPI27CD 66 MPI27 71 MPI27CD 68 Orifice DMS 0 2 000 Feet 0 610 M u 38 53 uUnit factory equipped for 0 2000 FT 0 ...

Page 13: ...D Figure 3 Minimum Fireplace Cavity Figure 2 Insert Dimensions 26 5 8 676mm 16 3 4 425mm 8 3 4 222mm 10 7 8 276mm 14 7 8 378mm 17 7 8 454mm 14 3 8 365mm 20 3 4 527mm O D 2 15 16 75mm Minimum Fireplace Opening A 27 686mm Front Opening Width B 18 457mm Height C 17 432mm Rear Width D 15 381mm Fireplace Depth ...

Page 14: ...tandoffsorsurfacestocombustibleconstruction etc above the appliance Paint or lacquer used to finish the mantel must be heat resistant in order to avoid discoloration Facing and Mantel Clearances see Figure 4 The letters in Figure 4 A through E show minimum clearances required from the appliance to combustibles and the minimum projection of the hearth extension Figure 4 Clearances Insert Leveling A...

Page 15: ...ing and Termination Cap 46DVA CL33 Preparation For Flex Liner Installation The liner connector plate can be removed as shown in Figure 6 to make it easier to connect the flex liners to the intake and exhaust collars Re install the liner connector plate when the insert is placed in the fireplace NOTE Ensuregasketonconnectorplateisnotdamagedbeforere installing INSTALLATION Figure 6 Intake Liner Conn...

Page 16: ... not operate When done assure all connections are securely fastened NOTE Theminimumverticalrise exhaustvent is10feet 3 1M andthe maximum vertical rise is 25 feet 7 6 M These dimensions are measured from the base of the unit to the end of the vent pipe The fireplace and fireplace chimney must be clean and in good working order and constructed of non combustible materials Inspect chimney cleanouts f...

Page 17: ...amenée du gaz un orifice d au plus 38 1 mm 1 5 po peut être pratiqué selon les règles de l art dans la partie inférieure des parois ou au fond de la chambre de combustion Cet orifice doit être obturé au moyen d isolant incombustible une fois la conduite de gaz en place The installer must mechanically attach the marking supplied with the gas fireplace insert to the inside of the firebox of the fire...

Page 18: ...3 Figure 14 4 Place a layer of glowing embers rockwool directly over the ports Figure 11 A light layer will give a more constant rear flame A heavy layer will give more glow but may need to be adjusted after light up to prevent sooting and poor flame quality 5 Place volcanic stones around the perimeter of the glowing embers rockwool in the areas shown in Figure 12 IMPORTANT Do not cover ports with...

Page 19: ... supplied with this manual Figure 16 Surround Mounting Tab Surround Mounting Tab Facade Mounting Tab Figure 15 Firebox Media Installation Optional kit See Page 35 for ordering information 1 Measure out approximately 3 cups of glass media and place an even layer on burner as shown in Figure 15 Care should be taken to NOT block pilot opening in burner tray or mound up media 2 Remove reflective accen...

Page 20: ...ting insert a small flat blade screwdriver into the tap and turn a half turn counter clockwise Cover the tap with the line from the manometer and check the pressure Again close the tap gently but securely after completing the check Check the taps for gas leaks with a gas leak test solution retighten if necessary If the pressure is not sufficient make sure the gas supply line is large enough the su...

Page 21: ...ust the air shutter slide the adjustment lever side to side see Figure 18 CAUTION The air shutter should never be set so as to make the tips of the flames sooty or create sooting on the viewing glass logs or heat exchanger If soot begins to form after burning the air shutter should be opened gradually until the sooting condition stops Gas quality and gas pressure may vary which can affect the burn...

Page 22: ...tric power to the appliance if service is to be performed 3 Close the main line gas shut off valve WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B BEFORE OPERATING smell all a...

Page 23: ...standing pilot simply by using the remote to switch from IPI to CPI This is done when the remote is in the off position Press the mode key and use the up down arrow key to change between IPI and CPI To save energy switch to intermittent mode To have a standing pilot which will help startup during cold climate conditions by warming the flue and the glass switch to standing pilot The standing pilot ...

Page 24: ...ystem or activating manual bypass of the remote system CAUTION Propertydamagehazard Excessiveheatcancause propertydamage Theappliancecanstaylitformany hours Turn off the appliance if it is not going to be attended for any length of time Always place the Transmitter where children can not reach it Figure 22 Remote transmitter Figure 21 ON OFF Key THERMOSTAT Key UP DOWN Arrow Key MODE Key Blue LCD D...

Page 25: ...s turned off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is off the flame will come on in the high position see Figure 25 A single beep will confirm reception of the command Room Thermostat Remote Operation The Remote Control can operate as a room thermostat The thermostat can be set to a desired temper...

Page 26: ... heat up and the flames will become a yellow orange color Adjusting the appliance to cause the flames to turn orange sooner may result in poor combustion sooting and a hazardous situation See Figure 26 showing proper flame appearance When testing for proper operation If an optional thermostat is installed adjust it to its highest temperature setting Visually determine that main burner gas is burni...

Page 27: ... commandes étiquetez tous les fils avant de les débrancher Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux VALVE BURNER PILOT ON OFF SWITCH PILOT ROOM AIR BLOWER BATTERY HOLDER ACCENT LIGHT POWER CORD GRN YLW BLK BRN YLW ORG ORG RED BLK WHT BLK WHT GRN GRN YLW ORG WHT GRN WHT BLU BLU BLK 1 4 PRG BUTTON X6 X5 X4 X3 X2 X1 X10 X11 FEMALE DISCONNECT MALE DISCONNECT ST...

Page 28: ...an those approved for use with this appliance o Check that the chimney and its outlet are open and free of soot block age or debris The venting system should be periodically examined by a qualified agency o Check gaskets once a year Gaskets must be tight Replace if neces sary o Periodically inspect the pilot system for proper flame Turn the pilot ON Auto switch to the ON position Ensure the ignite...

Page 29: ...on these doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptibletodamage Donotscratchorhandle roughly while reinstalling the glass door frame The glass door s of this appliance must only be replaced as a complete unit as provided by the manufacturer Donotattempttoreplacebroken cracked or chipped glass separately Do not attempt to touch the front enclosure ...

Page 30: ...lectrical Code Part 1 CSA C22 1 latest edition See Operating Options for burner ON OFF switch information Figure 31 Blower Assembly Removal Blower Assembly Fireplace Insert Back Repair If the glass is broken in the glass door the entire door metal frame gasket and glass should be replaced as a unit This replacement glass door is available from your IHP dealer Do not use substitute parts or materia...

Page 31: ...emporary and Santa Fe Facades a Using a 3 8 nut driver remove and set aside the four nuts and Z brackets holding each corner of the barrier in place b Remove the damaged barrier from the facade and discard Deco Facades a Using a 3 8 nut driver remove and set aside the two nuts and Z brackets holding the top corners of the barrier in place b Using a flat blade screwdriver careful pry up the two tab...

Page 32: ...on on Page 17 through 20 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot flame is not engulf ing the sensor Obstructed vent system Check the gas supply and gas shutoff valves Checkcontrolcompartmentforanyobviousloosewiring callaservicetechnicianifrequired Call for a service technician Call for a service technician Nothi...

Page 33: ...rd Thermal Barrier Kit 14 H9178 Façade Mounting Bracket Kit set of two 15 H9183 Refractory Panel Retaining Bracket Kit two sets one of each style 16 H9181 Media Burner Support Tray Kit MPI27CD only 17 H9170 Media Burner Assembly includes shutter assy MPI27CD only 18 H9182 Media Burner Accent Glass MPI27CD only 19 H9180 Log Support Panel Kit MPI27 only 20 H9169 Log Burner Assembly MPI27 only 21 H91...

Page 34: ...34 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS MPI27 MPI27CD 1 2b 4 5 6 7 8 9 10 11 12 13 14 15 16 3a 3b 17 20 19 21 22 23 2a 18 24 25a 25b 26 3A 3B 3b 3a ...

Page 35: ... MPI27 Madison Park 27 Small Insert 87 5 lb 12 22 cu ft H9123 MPI27CD Madison Park Contemp 27 Small Insert 80 lb 12 22 cu ft Surround Kits required accessory Cat No Model Description H9131 FP2637 MPDVI27 3 Sided Surround 37 W x 26 H H9132 FP2641 MPDVI27 3 Sided Surround 41 W x 26 H H9133 FP3037 MPDVI27 3 Sided Surround 37 W x 30 H H9134 FP3041 MPDVI27 3 Sided Surround 41 W x 30 H H9135 FP3846 4S M...

Page 36: ...38mm Du bas de l appareil au dessous de la finition supérieure 32 813mm B Mur de côté 9 1 2 241mm C 6 152mm manteau de foyer à partir de la base 34 864mm PROTECTION DU FOYER D Distanceverticaledelabasede 0 4 del appareilàl extensiond âtre 0mm 102mm E Extensiond âtremin àl avant 10 0 del appareil 254mm 0mm Voir le manuel d entretien pour les informatinos supplémentaires reliées aux distances à resp...

Page 37: ...SI NFPA 54 DERNIÈRE ÉDITION ETATS UNIS OU CAN CGA B149 1 DERNIÈRE ÉDITION CANADA CET APPAREIL DOIT ÊTRE INSTALLÉ SELON LES DIRECTIVES D INSTALLATION DU FABRICANT POUR INSTALLATION DANS DES FOYERS À COMBUSTIBLE SOLIDE SEULEMENT DE MAÇONNERIE OU PRÉFABRIQUÉ EN USINE CE FOYER RADIANT AU GAZ À ÉVACUATION N EST PAS CONÇU POUR ÊTRE UTILISÉ AVEC DES FILTRES À AIR CET APPAREIL DOIT ÊTRE UTILISÉ AVEC LE TY...

Page 38: ...entraînant des dommages des blessures ou la mort A Cet appareil est muni d un dispositif d allumage qui allume automatiquement la veilleuse Ne tentez pas d allumer la veilleuse manuellement B AVANT DE FAIRE FONCTIONNER reniflez tout autour de l appareil pour déceler une odeur de gaz Reniflez près du plancher car certains gaz sont plus lourds que l air et peuvent s accumuler au niveau du sol QUE FA...

Page 39: ...mage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d damages repairs or inefficiency resulting from faulty installation or application of the Product IHP is not responsible for inadequate fireplace system draft caused by air cond...

Page 40: ... your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions conce...

Reviews: