39
Parameter 1 & Interface Display
Parameter 2 Description
Charger Float Voltage Setting
Display: 15
Parameter 2: Charger Float Voltage
2.20 – 2.33:
Set the charger float voltage
from 2.20 V/cell to 2.33 V/cell (Default:
2.28V/cell)
EPO Logic Setting
Display: 16
Parameter 2: EPO Function Control
Logic
AO:
Active Open (Default). When this
is selected, it will activate EPO function
with Pin 1 and Pin 2 in open status
AC:
Active Close. When this is selected,
it will activate EPO function with Pin 1
and Pin 2 in close status
Site Fault Detection Enable/ Disable
Display: 17
Parameter 2: Enable / Disable Site
Fault Detection You May Choose the
Following Two Options
ENA:
Site fault detection enable (Default)
DIS:
Site fault detection disable
Summary of Contents for GBB1000N
Page 2: ......
Page 52: ... 2020 IOGEAR ...