45
Specifications
Model Name
GBB1000N
GBB1500N
GBB2000N
GBB3000N
General
UPS Topology
Double-Conversion
Energy Saving (max)
>96% (ECO)
>89% (AC)
>88% (Batt)
>96% (ECO)
>89% (AC)
>88% (Batt)
>96% (ECO)
>90% (AC)
>90% (Batt)
>96% (ECO)
>91% (AC)
>90% (Batt)
Input
Voltage
100/110/115/120/125/127 (127 is not applicable to US voltage)
Input Voltage Range
80-150 VAC ± 5% @ 100% load
55-150 VAC ± 5% @ 50% load
Derate capacity to 90% when the output voltage is adjusted to
100VAC
Input Frequency Range 40Hz – 70Hz
Rated input current
9.3A
13.2A
17.6A
26.4A
Input Power Factor
≥
0.99 @ nominal voltage (100% load)
Cold Start
Yes
Plug Type
NEMA 5-15P
NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
Power Cords
6ft
Output
VA
1000
1500
2000
3000
Watts
1000
1430
1930
2850
On Battery Waveform
Sine Wave
On Battery Voltage
100/110/115/120/125/127 VAC models (127 is not applicable to
US voltage)
On Battery Frequency
50/60Hz ± 3Hz
Total Outlets
8
7
Outlet Type
(8) NEMA 5-15R
(8) NEMA
5-20R
(6) NEMA
5-20R +
(1) NEMA L5-
30R
Outlets – Battery &
Surge Protected
Except GBB3000N is 7, other models are 8
Rated Power Factor
>0.96
0.97
0.97
0.96
Crest Factor
3:1