34
Parameter 1 & Interface Display
Parameter 2 Description
ECO Voltage Range Setting
Display: 05
Display: HS
Parameter 2: Acceptable high
voltage point and low voltage point
for ECO Mode.
Press the Up or Down
key to adjust the values
HLS:
High Loss Voltage in ECO Mode in
Parameter2
For 100/110/115/120/127 VAC models
(127 is not applicable to US voltage), the
setting range is from +3V to +12V of the
nominal voltage
(D6V)
LLS:
Low Loss Voltage in ECO Mode in
Parameter2
(Default -12V)
For 100/110/115/120/127 VAC models
(127 is not applicable to US voltage), the
setting voltage is from -3V to -12V of the
nominal voltage
(Default -6V)
Enable / Disable Bypass when UPS is off
Display: 06
Parameter 2: Enable or Disable
Bypass Function
You may choose between below 2
options:
ENA:
Enable Bypass
DIS:
Disable Bypass (Default)