Goodrive20-EU Series VFD
Function parameters
-44-
Function
code
Name
Description
Default Modify
1: Switch at the start frequency
2: Switch after the speed reaches the stop speed
(P01.15) for the set the delay (P01.24)
P01.15
Stop speed
0.00
–100.00Hz
0.50Hz
◎
P01.16
Detection of
stopping speed
0: Detect at the setting speed
1: Detect at the feedback speed (valid only for
vector control only)
1
◎
P01.17
Detection time
of the feedback
speed
When P01.16=1, the actual output frequency of
the VFD is less than or equal to P01.15 and is
detected during the time set by P01.17, the VFD
will stop; otherwise, the VFD stops in the time set
by P01.24.
T
Stop speed
A
Ramp reference
frequency
Output frequency
Frequency
P01.24
P01.17
B
C
Running A
Running B
Running C
Setting range: 0.00
–100.00s ( valid only when
P01.16=1)
0
.50
s
◎
P01.18
Power-on
terminal
running
protection
selection
When the running command channel is the
terminal control, the system will detect the state
of the running terminal during powering on.
0: The terminal running command is invalid when
powering on. Even the running command is
detected to be valid during powering on, the VFD
won't run and the system keeps in the protection
state until the running command is canceled and
enabled again.
1: The terminal running command is valid when
powering on. If the running command is detected
to be valid during powering on, the system will
start the VFD automatically after the initialization.
Note:
This function should be selected with
cautions, or serious result may follow.
0
○