Goodrive20-EU Series VFD
Function parameters
-66-
Function
code
Name
Description
Default Modify
BIT3
BIT2
BIT1
BIT0
RO2
RO1
Reserved
Y1
Setting range: 0
–F
P06.06
Y1 open delay
time
Setting range: 0.000
–50.000s
0.000s
○
P06.07
Y1C off delay
time
Setting range: 0.000
–50.000s
0.000s
○
P06.10
RO1 switching
on delay time
The function code defines the corresponding
delay time of the electrical level change during
the programmable terminal switching on and off.
RO electric level
RO valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000
–50.000s
0.000s
○
P06.11
RO1 switching
off delay time
0.000s
○
P06.12
RO2 switching
on delay time
0.000s
○
P06.13
RO2 switching
off delay time
0.000s
○
P06.14
AO1 output
selection
0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Running speed (relative to twice the motor
synchronous rotational speed)
4: Output current (relative to twice the rated VFD
current)
5: Output current (relative to twice the rated
motor current)
6: Output voltage (relative to 1.5 times the rated
VFD voltage)
7: Output power (relative to twice the rated motor
power)
8: Set torque value (relative to twice the rated
motor torque)
9: Output torque (relative to twice the rated motor
torque)
10: Analog AI1 input value
11: Analog AI2 input value
12: Analog AI3 input value
13: High-speed pulse HDIA input value
14: Value 1 set through Modbus communication
0
○
P06.15
AO2 output
selection
0
○
Summary of Contents for Goodrive20-EU VFD Series
Page 1: ......
Page 173: ...6 6 0 0 1 0 0 4 8 4...