Goodrive20-EU Series VFD
Communication protocol
-133-
Function
Address
Data description
R/W
characteristics
=10: communication control
VFD fault code
2102H
See the fault type instruction
R
Identifying code of
the VFD
2103H
GD20-EU-----0x0180
R
Operation frequency
3000H
0
–Fmax,
unit:
0.01Hz
Compatible with
the
communication
addresses of
GD, CHF100A,
and CHV100
series.
R
Setting frequency
3001H
0
–Fmax,
unit:
0.01Hz
R
Bus voltage
3002H
0.0
–2000.0V, unit:
0.1V
R
Output voltage
3003H
0
–1200V, unit: 1V
R
Output current
3004H
0.0
–3000.0A, unit:
0.1A
R
Operation speed
3005H
0
–65535,
unit:
1RPM
R
Output power
3006H
-300.0
–300.0%,
unit:
0.1%
R
Output torque
3007H
-250.0
–250.0%,
unit: 0.1%
R
PID setting
3008H
-100.0
–100.0%,
unit: 0.1%
R
PID feedback
3009H
-100.0
–100.0%,
unit: 0.1%
R
Input state
300AH
000
–1FF
R
Input state
300BH
000
–1FF
R
AI 1
300CH
0.00
–10.00V, unit:
0.01V
R
AI 2
300DH
0.00
–10.00V, unit:
0.01V
R
AI 3
300EH
-10.00
–10.00V,
unit: 0.01V
R
AI 4
300FH
Reserved
R
Read high speed
pulse 1 input
3010H
0.00
–50.00kHz,
unit: 0.01Hz
R
Read high speed
pulse 2 input
3011H
Reserved
R