Goodrive20-EU Series VFD
Function parameters
-78-
Function
code
Name
Description
Default Modify
the multi-function digital output terminals will
output the signal of "running time arrival".
Setting range: 0
–65535min
P08.28
Time of fault
reset
The time of the fault reset: set the fault reset time
by selecting this function. If the reset time
exceeds this set value, the VFD will stop for the
fault and wait to be repaired.
The interval time of the fault reset: The interval
between the time when the fault occurs and the
time when the reset action occurs.
Setting range of P08.28: 0
–10
Setting range of P08.29: 0.1
–100.0s
0
○
P08.29
Interval time of
automatic fault
reset
1.0s
○
P08.30
Frequency
decreasing
ratio in drop
control
The output frequency of the VFD changes as the
load. And it is mainly used to balance the power
when several VFDs drive one load.
Setting range: -50.00Hz
–50.00Hz
0.00Hz
○
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of "frequency level detect FDT"
until the output frequency decreases to a value
lower than (FDT electrical level
—FDT retention
detection value) the corresponding frequency,
the signal is invalid. Below is the waveform
diagram:
Output frequency
FDT level
Y,
RO1, RO2
FDT lag
Setting range of P08.32: 0.00Hz
–P00.03
(the max. frequency)
Setting
range
of
P08.33
and
P08.35:
0.0
–100.0%
50.00H
z
○
P08.33
FDT1 retention
detection value
5.0%
○
P08.34
FDT2 electrical
level detection
value
50.00H
z
○
P08.35
FDT2 retention
detection value
5.0%
○
Summary of Contents for Goodrive20-EU VFD Series
Page 1: ......
Page 173: ...6 6 0 0 1 0 0 4 8 4...