Function Parameters
59
Function
code
Name
Description
Default
value
Modify
terminal status can be changed only through
communication, and the communication address
is 0x200A.
E05.13
Terminals
control running
mode
Set the operation mode of the terminals control
0: 2-wire control 1, comply the enable with the
direction. This mode is widely used. It determines
the rotation direction by the defined FWD and REV
terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Hold on
Forward
running
Reverse
running
1: 2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the
enabling ones. The direction depends on the state
of the defined REV.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Stopping
Forward
running
Reverse
running
2: 3-wire control 1; Sin is the enabling terminal on
this mode, and the running command is caused by
FWD and the direction is controlled by REV. Sin
is natural closed.
COM
K
SB2
SB1
FWD
REV
SIn
0
◎