background image

17

Altitude

Gas

Kit

Manifold

Pressure

Pressure

Sensor 

Natural

None

0 - 4500

None

3.0" w.c.

Table 5

Gas Piping Connections

T

O

 

AVOID

 

POSSIBLE

 

UNSATISFACTORY

 

OPERATION

 

PMENT

USE

 

THE

 

PROPER

 

SIZE

 

OF

 

NATURAL

 

GAS

 

PIPING

 

NEEDED

 

WHEN

 

RUNNING

 

PIPE

 

FROM

 

THE

 

METER

 

TO

 

THE

 

FURNACE

.

OR

 

EQUIPMENT

 

DAMAGE

 

DUE

 

TO

 

UNDERFIRING

 

OF

 

EQU

I

WARNING

When sizing gas lines, be sure to include all appliances  on the 

same gas supply line and which will operate simultaneously.
The gas piping supplying the furnace must be properly sized 

based on the gas flow required, specific gravity of the gas, 

and length of the run.  The gas line installation must comply 

with local codes, or in their absence, with the latest edition of 

the National Fuel Gas Code, NFPA 54/ANSI Z223.1.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

Nominal Black  Pipe Size

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on

0.60 Specific Gravity Gas)

CFH = BTUH Furnace Input   

Heating Value of Gas (BTU/Cubic Foot)

Table 6

To connect the furnace to the building’s gas piping, the installer 

must supply a ground  joint union, drip leg, manual shutoff 

valve, and line and fittings to connect to gas valve.  In some 

cases, the installer may also need to supply a transition piece 

from 1/2” pipe to a larger pipe size.
The following stipulations apply when connecting gas piping.  

• 

Gas piping must be supported external to the furnace 

cabinet so that the weight of the gas line does not 

distort the burner rack, manifold or gas valve. 

• 

Use black iron or steel pipe and fittings for the building 

piping. Where possible, use new pipe that is properly 

chamfered, reamed, and free of burrs and chips. If 

old pipe is used, be sure it is clean and free of rust, 

scale, burrs, chips, and old pipe joint compound. 

• 

Use  pipe  joint  compound  on  male  threads  ONLY. 

Always use pipe joint compound (pipe dope) that 

is APPROVED FOR ALL GASSES. DO NOT apply 

compound to the first  two threads.

• 

Use ground joint unions.

• 

Install a drip leg to trap dirt and moisture before it can 

enter the gas valve.  The drip leg must be a minimum 

of three inches long.

• 

Install a 1/8” NPT pipe plug fitting, accessible for test 

gage connection, immediately upstream of the gas 

supply connection to the furnace.

•  Always use a back-up wrench when making the 

connection to the gas valve to keep it from turning. 

The orientation of the gas valve connection is 374 

in-lbs; excessive over-tightening may damage the 

gas valve and/or gas manifold assembly. 

•  Install a manual shutoff valve between the gas 

meter and unit within six feet of the unit.  If a union 

is installed, the union must be downstream of the 

manual shutoff valve, between the shutoff valve and 

the furnace.

• 

Tighten all joints securely.

•  Protect connectors and semi-rigid tubing against 

physical and thermal damage when installed.  Ensure 

aluminum-alloy tubing and connectors are coated to 

protect against external corrosion when in contact 

with masonry, plaster, or insulation, or subjected to 

repeated wetting by liquids such as water (except rain 

water), detergents, or sewage. The gas piping may 

enter the left or right side of the furnace cabinet. The 

installer must supply rigid pipe long enough to reach 

the outside of the cabinet to seal the grommet cabinet 

penetration. A semi-rigid connector to the gas piping 

can be used outside the cabinet per local codes. 1/2” 

NPT pipe and fittings are required. Model requires 

one 90 deg elbow, one 2” nipple and additional nipple 

to reach outside the cabinet. A semi-rigid connector 

to the gas piping can be used outside the cabinet 

per local codes. From the elbow, the length of pipe 

and the fittings required will vary by the side chosen, 

location of union and cabinet width. The union may 

be placed inside or outside of the cabinet.

General Furnace Layout

Figure 11

Summary of Contents for MES80

Page 1: ...ION 6 LOCATION REQUIREMENTS AND CONSIDERATIONS 7 Clearances and Accessibility 8 Installation Positions 8 Venting For Horizontal Left Or Right Installations 8 Horizontal Installation 8 Furnace Suspensi...

Page 2: ...ustment 23 Gas Input Rate Measurement Natural Gas Only 23 Temperature Rise 24 Circulator Blower Fan Timing Adjustment 24 OPERATIONAL CHECKS 25 Checking Duct Static 25 SAFETY CIRCUIT DESCRIPTION 25 Gen...

Page 3: ...ce qui peut entra ner la mort des blessures ou des dommages mat riels IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL I...

Page 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Page 5: ...ing precautions during furnace installation and servicing to protect the integrated control module from damage By putting the furnace the control and the person at the same electrostatic potential the...

Page 6: ...furnace A return air temperature range between 60 F 16 C and 80 F 27 C is maintained Air filters are installed in the system and replaced daily during construction and upon completion of construction...

Page 7: ...icals halogen type refrigerants printing inks cleaning solutions such as perchloroethylene paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers m...

Page 8: ...gas electrical and drain line connections NOTE In addition to the required clearances to combustible materials a minimum of 24 service clearance must be available in front of the unit Installation Po...

Page 9: ...ndition c In so far as practical close all building doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the build...

Page 10: ...oset or utility room must have two ventilation openings with a total minimum free area of 0 25 square inches per 1 000 BTU hr of furnace input rating Refer to Specification Sheet applicable to your mo...

Page 11: ...PPED APPLIANCE THE POTENTIAL FOR CONDENSATION DAMAGE MAY STILL EXIST WITH EXTREMELY COLD CONDITIONS LONG VENT CONNECTORS EXTERIOR CHIMNEYS OR ANY COMBINATION OF THESE CONDITIONS THE RISK OF CONDENSATI...

Page 12: ...existing metal liners are correctly installed and in good condition Remove the lowest existing vent connector and examine the inside of the elbow or tee at the base of the liner A small amount of soo...

Page 13: ...y recognized building codes or standards One such standard which may be referenced is the Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances ANSI NFPA 211 Remember that all appli...

Page 14: ...or thimbles must be used to prevent the B vent from coming into direct contact with the tile liner or chimney walls Direct contact would result in higher heat loss with an increased possibility of poo...

Page 15: ...s or by the rotation of the fan Also confirm that wiring location will not interfere with fil ter removal or other maintenance After the junction box is in the desired location use washers to connect...

Page 16: ...p in a fossil fuel application A fossil fuel application refers to a combined gas furnace and heat pump installation which uses an outdoor temperature sensor to determine the most cost efficient means...

Page 17: ...f old pipe is used be sure it is clean and free of rust scale burrs chips and old pipe joint compound Use pipe joint compound on male threads ONLY Always use pipe joint compound pipe dope that is APPR...

Page 18: ...size that the heat exchanger can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream The access panel must be made to prevent air leaks when the furn...

Page 19: ...be installed in the central return register or a side panel external filter rack kit upflows As an alternative a media air filter or electronic air cleaner can be used as the primary filter The follo...

Page 20: ...have 5 media filters and are available in the following configurations Consult your distributor for information on our complete line of IAQ Clean Comfort products Air cleaner installation location Ma...

Page 21: ...call for fan Circulator blower is de energized Electronic air cleaner terminals are de energized Furnace awaits the next call from thermostat Start up Procedure And Adjustment Furnace must have a 120...

Page 22: ...stem 3 Inlet pressure tap connections a White Rodgers valve Back inlet pressure test screw inlet pressure tap out one turn counterclockwise not more than one turn 4 Connect calibrated U tube manometer...

Page 23: ...regulator cover screw 10 Turn OFF all electrical power and gas supply to the system 11 Remove the manometer hose from the hose barb fitting or outlet pressure Tap 12 Replace outlet pressure tap a Whit...

Page 24: ...onvert capacity to tons Example Cooling Capacity of 30 000 BTU hr 30 000 12 000 2 5 Tons 2 Determine the proper air flow for the cooling system Most cooling systems are designed to work with air volum...

Page 25: ...Operational Checks TO AVOID PERSONAL INJURY OR DEATH DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS CONTACT A QUALIFIE...

Page 26: ...ure activated sensor It guards against overheating resulting from insufficient air passing over the heat exchanger The auxiliary limit control is suitable for both horizontal right and horizontal left...

Page 27: ...Y OR DEATH DISCONNECT ELECTRICAL POWER BEFORE REMOVING FILTERS NEVER OPERATE FURNACE WITHOUT A FILTER INSTALLED BECAUSE DUST AND LINT WILL BUILD UP ON INTERNAL PARTS RESULTING IN LOSS OF EFFICIENCY EQ...

Page 28: ...lthough only functional parts are shown in the parts list all sheet metal parts doors etc may be ordered by description Parts are available from your distributor Functional Parts List Gas Valve Natura...

Page 29: ...10 Integrated Control Module 11 Transformer 12 Blower Door Interlock Switch 13 Circulator Blower Component ID Tubular Heat Exchanger Pressure Sensor Assembly Flue Pipe Connection Gas Line Entrance Ga...

Page 30: ...in Electrostatic Discharge section of manual Furnace Fails to operate Control LED is flashing TWO 2 RED flashes 2 Flashes RED Pressure sensor indicates pressure reading when it should be zero Faulty...

Page 31: ...ockage or excessive wear and replace as needed Check and correct pressure sensor wiring Turn power OFF prior to repair Replace induced draft blower with proper replacement part LED is steady on Steady...

Page 32: ...combustion noise during heating Insufficient combustion air or high input Blocked flue and or air inlet pipe or faulty induced draft blower or pressure sensor Check and correct gas supply and manifol...

Page 33: ...7 26 1663 27 1620 1588 1546 Orange 898 49 794 NA 723 NA 656 NA 588 NA 522 449 384 Black 1443 31 1388 32 1339 33 1292 34 1242 36 1202 1155 1107 Brown 1601 28 1559 29 1513 29 1473 30 1413 31 1405 1365 1...

Page 34: ...D JUNCTION INTEGRATED CONTROL INTERNAL TO 0140F02416 A 2 MANUFACTUR S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS NOTES HI VOLTAGE FIE...

Page 35: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 36: ...ering your product is a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminish t...

Reviews: