Initial startup and operation
Speed setting via external analog signal
Above a voltage of > 1 V, the SPEED signal has higher priority than the speed setting by the internal DIP switches. The
speed of the RollerDrive is controlled by the external signal, irrespective of the position of the DIP switches.
¾
Set the speed of the RollerDrives by changing the external signal within a range of 1 to 10 V. Changes to the
signal will only be applied if they differ by at least 0.1 V from the previous value.
¾
Set the external signal to 0 V to enable the internal speed setting by the DIP switch.
The specified analog speed applies to all zones of the ZoneControl conveyor.
6.4
External influence on zero pressure accumulation conveying
The ZoneControl has two control signals to specifically influence the otherwise automatic conveyor process:
• ZONE_START
• ZONE_STOPP
These signals enable the current conveyor logic of a zone to be interfered with to the extent that locally generated
START-STOP processes can be integrated easily and simply into the parallel running global ZPA conveyor process.
Caution
Accidental start-up of the RollerDrive!
Danger of crushing of limbs and damage to goods!
¾
Before enabling the ZONE_START and ZONE_STOPP signals, ensure that no unauthorised persons are in
the conveyor’s hazard zones.
ZONE_STOPP
• Can be used at every zone.
• Package is conveyed to the zone sensor in the affected zone.
• When in-active, immediate transition to normal ZPA conveyor operation.
• The signal does not stop the RollerDrive immediately.