Chapter 4: Web configuration
212
NS3562-8P-2S User Manual
Object
Description
Classification mode:
System reserves PoE power to PD according to
PoE class level.
Consumption mode:
System offers PoE power according to PD real
power consumption.
Allocation mode:
Users can assign how much PoE power for per port
and the system reserves PoE power to the PD.
Temperature Threshold
Allows setting over temperature protection threshold value. If the
system temperature is overly high, the system will lower the total PoE
power budget automatically.
PoE Temperature
Displays the PoE chip temperature
Power Budget
Sets the PoE power budget limitation.
Current power consumption
The page includes the following fields:
Object
Description
PoE Mode
There are three PoE modes:
Enable
: Enables the PoE function.
Disable
: Disables the PoE function
Schedule
: Enables the PoE function in schedule mode
Schedule
Indicates the schedule profile mode. Possible profiles are:
Profile1
Profile2
Profile3
Profile4
Priority
Priority represents PoE port priority. There are three levels of
power priority:
Low
,
High
, and
Critical
.
Priority is used when total power consumption is over the total
power budget. In this case, the port with the lowest priority is
turned off and power is provided to the port with higher priority.
PD Class
Displays the class of the PD attached to the port, as
established by the classification process. Class 0 is the default
for PDs. The PD is powered based on PoE Class level if the
system is working in Classification mode. The PD will return to
Class 0 to 4 in accordance with the maximum power draw.
Current Used [mA]
The Power Used shows how much current the PD currently is
using.
Power Used [W]
The Power Used shows how much power the PD currently is
using.
Power Allocation
Limits the port PoE supply Watts. The per port maximum value
must less than 36 W, and total port values must less than the
power reservation value. After a power overload has been
detected, the port automatically shuts down and remains in
detection mode until the PD’s power consumption is lower than
the power limit value.