FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
39
6.4.2 230 V version (FP/FR1xxx/FR2000 models – except
FP1216EN &
FP1264)
6.4.2.1 Mains connection
Figure 29: FP/FR12xx/FR2000 connecting mains-to-mains terminal block
1. Mains terminal block
5. To earth stud on panel
2. Neutral
6. To transformer
3. Earth
7. Mains disconnect with fuse
4. Live
A mains terminal block with fuse is provided for connecting the panel to the mains. Please
note the polarity of live, mains and earth.
During installation, the 230 VAC should be fed directly from a separate group in the
distribution board. This group should have a bi-polar disconnect device, be clearly marked
and only be used for fire detection equipment.
The recommended mains cable is 3 x 1.5 mm² (live, neutral, earth).