background image

 

FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 

53 

8.2  Procedure for switching on 

1.  Switch the main power on at the power supply or connect the 24 V to the 24 V supply 

board. 

2.  The internal buzzer will sound and the product code will be displayed on the LCD 

screen along with the revision of host firmware, firmware code and the creation date 

of the firmware. 

If the above does not occur, DO NOT proceed. Check that the mains supply is 

present and that the fuses are good. 
 

3.  Switch the battery On/Off switch to the ON position (230 V model only). 

4.  Check that the battery float voltage is 27.6 V. If the voltage is significantly less, then 

check: 

• 

Are the batteries flat? 

• 

Are there possible overloads in the field? 

5.  If there are visible signs of the power supply overheating, then do not proceed. 

Disconnect the field wiring and batteries, and eliminate the cause of the problem. 

6.  The fire panel will perform internal checks. Any failures occurring will be reported on 

the LCD screen. 

Observe the total number of faults reported on line 8 of the LCD screen. 
It is expected to have at least two faults reported: 

• 

Memory unlocked 

• 

Service switch ON 

7.  Use the 

 key to view the faults existing. 

8.  All faults (except for the two above) should be eliminated before proceeding further. 

Use the [RESET] button to obtain a new fault report each time. 

Possible faults that can occur on switch ON are: 

y

  Loop overload 

- Check the affected loop for short circuits 

y

  Earth fault 

- Check/eliminate the fault 

y

  Battery fail 

- Check battery charging 

y

  Sounders or fire brigade  - Check 3K3 termination resistors 

y

  Short circuit or open circuit termination resistors 

y

  Specific device faults 

- Check device 

y

  Double address 

- Note address of device and check 

9.  Enable the loop devices of the FP2000 fire panel in one of three methods: 

• 

Individually manually using the Device Set-up Menu. 

• 

Set default using the System Default Set-up. 

• 

Program by means of a laptop computer using the RS232 port. 

10.  Eliminate any fire alarms and communications alarms reported. 

Summary of Contents for FP 1200 Series

Page 1: ...FP FR1100 1200 2000 Series Analogue addressable fire panels repeaters and emulators Installation and Commissioning Manual Revision 6 2 February 2003...

Page 2: ...ation Aritech is an Interlogix company www aritech com COPYRIGHT 2001 Interlogix B V All rights reserved Interlogix B V grants the right to reprint this manual for internal use only Interlogix B V res...

Page 3: ...types 25 6 FIELD CONNECTIONS 26 6 1 Loop output and input connections 26 6 1 1 FP12xx 26 6 1 2 FP2xxx 27 6 2 Connections 28 6 2 1 Loop connections 28 6 2 2 Programmable relay 30 6 2 3 Supervised outpu...

Page 4: ...51 7 1 1 FP FR1xxx 51 7 1 2 FP FR2xxx 51 7 2 Operation mode 51 7 3 Language inserts 51 8 COMMISSIONING A FP2000 SERIES FIRE PANEL 52 8 1 Before switching on 52 8 2 Procedure for switching on 53 APPEN...

Page 5: ...output s connection on SD2000 common I O board 31 Figure 21 Two configurations for relay outputs 1 3 B 31 Figure 22 Two configurations for relay output 4 B 32 Figure 23 Location of jumpers on sounder...

Page 6: ...guide only and is not to be used to replace any local building and or wiring codes Other manuals available are 1 Aritech 900 Series Detectors Installation Manual 2 Aritech 2000 Series Detectors Insta...

Page 7: ...9x441x109 11 FP24128 2xZE2064 4A 8B 126 128 Sentrol No 609x441x109 11 FP2864 4xZE2016 8A 16B 126 128 Sentrol Yes 804x441x109 15 FP28255 4xZE2064 8A 16B 126 128 Sentrol Yes 804x441x109 15 FB2400 0 4A 8...

Page 8: ...80 NC NE2011 230 VAC 1 5 OPTIONS Compatibility with Extra Modules Description FP1216 FP1216EN 2416 2432 2864 FP1264 2464 24128 28255 FB2x00 FR1200 FR2000 2032 2064 FR2012 8 20255 LC2002 Loop driver ex...

Page 9: ...R20xx FC2011 2 x DB9 ports Real Time Clock with battery backup LCD1200 FP11xx 12xx FR12xx LCD1200 No LCD backlight LCD2000 2011 FP FR2xxx LCD2011 LCD backlight SOFTWARE Software Package Description PC...

Page 10: ...tallation and Commissioning Manual Fault disablements from addressable points Output to fault warning routing equipment Standardised input output interface according to DIN 14661 Test condition Total...

Page 11: ...ad 500 mA Loop operating load 100 mA maximum Zone capacity 16 or 64 zones expandable to 32 128 48 192 or 64 255 zones in cabinet size B 112 zones for control purposes LCD screen Backlit alphanumeric 8...

Page 12: ...expandable to 32 128 48 192 or 64 255 Indicators related to network facilities All 1 x LED Amber Panel 1 x LED Amber Membrane keyboard 1 2 3 4 5 6 7 8 9 0 A Z General control keys Silence buzzer Rese...

Page 13: ...only SD2000 board used OUT 1 Output to alarm devices Sounders A 24 V 100 mA supervised Supervision at 5V max B 3K3 680 Ohm switched output A 24 V 0 8 A supervised Supervision at 5 V max B 3K3 680 Ohm...

Page 14: ...SD2000 board used Sounder card 4 x supervised inputs inputs 1 4 3 3 kOhm termination 4 x supervised inputs inputs 1 4 3 3 kOhm termination 4 x supervised inputs inputs 1 4 3 3 kOhm termination FEP boa...

Page 15: ...t Fuses AC fuse 0 8 A 250 V T 20 mm STD fuse AC fuse 2 A 250 V T 20mm STD fuse AC fuse 2 A 20 mm STD fuse Aux Output 5 A 20 mm STD fuse Battery fuse 5 A 20 mm STD fuse Fuse 1 A 20 mm STD fuse Maximum...

Page 16: ...mA 200 mA 566 mA Normal Operation FP2416 2464 FP2432 24128 FP2864 FP28255 Mains load maximum 200 VA 200 VA Total output current 27 6 V 4 A 4 A Battery capacity IAUX 0 72H standby 36 AH 58 AH Battery...

Page 17: ...54 IP54 Temperature Operational 5 C to 40 C Storage 20 C to 60 C Operational 5 C to 40 C Storage 20 C to 60 C Operational 5 C to 40 C Storage 20 C to 60 C 4 MOUNTING INSTRUCTIONS 4 1 FP FR12xx 4 1 1 P...

Page 18: ...nting instructions Figure 2 Top bottom cable entries 1 Panel front A Bottom view 2 Rear mounting surface B Top view 3 Panel top C Rear panel view 4 Panel bottom 1 440 mm for the FP1216EN FP1264 5 Cabl...

Page 19: ...g of wires 2 Battery link 19 ARCNET network card top optional 3 Battery terminal red 20 Battery terminal black 4 Mains terminal block 21 Battery and power supply connection terminals 5 Earth stud 22 M...

Page 20: ...200 2000 V6 Installation and Commissioning Manual 4 2 FP2xxx 4 2 1 Panel dimensions Figure 4 Panel dimensions cabinet size A Cabinet size B 804 x 441 x 109 mm H x W x D Cabinet size C 473 5 x 441 x 10...

Page 21: ...Mounting instructions Figure 5 Mounting instructions A Cabinet size A C Cabinet size C B Cabinet size B 1 4 x 5 mm mounting holes The 5 mm mounting holes are located as shown in Figure 2 Five 20 mm h...

Page 22: ...uding batteries Figure 6 Cable entries CAUTION Mains wires 230V must enter the cabinet from the left bottom hole in the cabinet only Top entry violates EN60950 IEC950 safety requirements and will caus...

Page 23: ...wer supply board 6 RS232 ports DB 9connectors port 1 front port 2 back 20 Bus termination card 7 DB9 DB25 adapter with modem 21 DIP switch 8 Front end processor board 22 Zone matrix display board 9 FE...

Page 24: ...backlight board 12 Zone matrix display board 4 Host processor board 13 Optional internal printer PR2000 5 Current loop terminal connections 14 Service commission mode switch 6 RS232 ports DB 9 connec...

Page 25: ...ation and Commissioning Manual 23 5 LOOP DESIGN FP12XX FP2XXX FB2X00 ONLY 5 1 Typical configuration The fire panel accepts the following loop configurations Figure 9 Class A return loop Figure 10 Clas...

Page 26: ...900 Series and 2000 Series detectors EN54 specifies that a short circuit or an interruption in a detection circuit cannot prevent the indication of a fire alarm from more than 32 fire detectors and or...

Page 27: ...re than 100 ohm and the maximum loop capacitance in parallel with this should not exceed 1uF This will ensure that 126 900 Series or 128 2000 Series detectors can be operated over a distance of 2 km T...

Page 28: ...arm devices 2 Power supply board 10 General input FP1216 64 only 3 Loop driver 11 Fault routing return input FP1216 64 only 4 Sounder board 12 Fire protection return input FP1216 64 only 5 Programmabl...

Page 29: ...ctions 1 FEP 9 Fire alarm devices 2 Power supply board 10 General input 3 Line driver 11 Fault routing return input 4 Sounder board 12 Fire protection return input 5 Programmable relays 13 Fire brigad...

Page 30: ...Chapter 5 Loop design Figure 15 Class A loop connection 1 Forward 3 Loop 1 2 Return 4 Loop 2 When class B operation is required the A jumpers should be removed to double the amount of loops The B jump...

Page 31: ...oop cards in a panel must be configured in the same way either A or B Loop devices The FP2000 Series of analogue addressable fire panels are fully compatible with the Aritech 900 range of detectors an...

Page 32: ...indicates the state of the relays Figure 19 Programmable relay connections 1 Programmable relay 4 Out8 7 Output 6 switched LED indication 2 Programmable relay 3 Out7 8 Output 5 switched LED indicatio...

Page 33: ...relay coil resistance Polarity non reversed 2 Fire protection device Out3 Termination resistor 3k3 Including relay coil resistance Polarity non reversed 4 Fire alarm device Out1 Termination resistor...

Page 34: ...The LED is ON when there is no fault Figure 22 Two configurations for relay output 4 B Outputs CONFIG 1 CONFIG 2 Fault routing OUT4 J6 in J7 out J6 out J7 in Figure 23 Location of jumpers on sounder b...

Page 35: ...e located on the sounder PCB The function of these inputs is determined by the operation mode of the FP2000 see Appendix B In EN NEN and EP operation mode these inputs have no dedicated function and a...

Page 36: ...d on the FEP PCB Each input is opto isolated and independent of polarity These inputs are not supervised and can be used through I O programming Figure 25 Auxiliary inputs 1 Auxiliary input 1 5 Sectio...

Page 37: ...264 The Aritech dual tone siren can be connected on Sounder out 1 and Fire Brigade out 2 in the following way Figure 26 Dual tone siren connections 1 Common 4 Out2 2 Sound 5 Out1 3 Sound Set jumpers a...

Page 38: ...que address by means of resistor settings at that panel Please refer to the appropriate Installation Manual for the correct settings The location of the current loop terminal connections is shown in F...

Page 39: ...XD 3 TXD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 9 RI To route the RS232 cable inside the cabinet refer to section 4 When connecting the null modem cable the pins on both sides of the cable must be connected as...

Page 40: ...connections 6 4 1 24 V version FR2xxx models The FR2000 is delivered with a 24 V connection board Figure 28 FP FR2xxx power supply connections 24 V version 1 24 VDC termination board 4 Earth 2 24 V 5...

Page 41: ...tral 6 To transformer 3 Earth 7 Mains disconnect with fuse 4 Live A mains terminal block with fuse is provided for connecting the panel to the mains Please note the polarity of live mains and earth Du...

Page 42: ...30 FP FR12xx power supply and fault relay connections 1 Black 7 Vin connection 2 Link 8 VR3 LCD contrast adjuster 3 Red 9 Modem MOD2000 connection 4 12 V Batteries 10 Start up 5 Host CPU connection 11...

Page 43: ...the wires away from sharp edges and corners and fix them into position Figure 31 FP FR12xx power supply s fault relay connections 1 Normally open 3 Normally closed 2 Common Fault output NC Jumpers def...

Page 44: ...r supply and transformer connections 1 Mains terminal block 10 Transformer TRF1200 2 Neutral 11 Power Supply PS1200S77 3 Ground 12 Vin 4 Live 13 Bat 5 Mains switch with fuse 14 Black 6 To ground stud...

Page 45: ...ed according to EN54 4 A mains switch on the bottom is provided as well as a battery ON OFF switch Three LED s on top of the power supply indicate the following Charger On Battery On Battery fail On t...

Page 46: ...her equipment may be connected to the battery terminations The PSU 2000 is designed for use in Aritech fire panel housing only An optional third source battery 9 V PP3 can be installed as a third sour...

Page 47: ...lephone line refer to Figure 3 Figure 7 and Figure 34 5 Connect the green earth wire leading from the modem to the earth stud inside the fire panel Please note that the modem and associated circuitry...

Page 48: ...ction diagram 1 To 5 V on power supply modem terminal 8 To earth 2 5 V to printer not used fixed in position to prevent contact 9 Green 3 Telephone line adapter if required 10 Phone 4 To telephone lin...

Page 49: ...etwork card installed as a standard The PCB is delivered with the necessary washers nuts and spacers to allow for proper mounting All repeaters emulators are supplied with a standard NC2011 RS485 netw...

Page 50: ...de the user the ability to implement a wide range of network topologies when networking FP2000 Series fire panels and FR2000 Series repeaters emulators The modules are delivered with the necessary was...

Page 51: ...The FC1200 2011 board has a 20 pin male connector pin on which the LON2000 board must be mounted The PCB is delivered with the necessary washer nut and spacer to allow for proper mounting Figure 37 Mo...

Page 52: ...lay This viewing angle is set by adjusting potentiometer VR 1 located on the LCD display and backlight board Figure 39 Adjustment of the LCD viewing angle 1 LCD display and backlight board 2 VR1 LCD c...

Page 53: ...e panel is used to select the language Please refer to Appendix A SW1 SW2 SW3 determine the language 7 2 Operation mode NEN EN VdS or EP mode of operation is selectable The operation of Sounder Fire B...

Page 54: ...aters Fireman s panels to the current loop terminals For detail refer to the FM800 Installation Configuration and Detailed Operation Manual 10 Connect the network card if necessary for detail refer to...

Page 55: ...orm internal checks Any failures occurring will be reported on the LCD screen Observe the total number of faults reported on line 8 of the LCD screen It is expected to have at least two faults reporte...

Page 56: ...lts that are reported 3 Check status of the systems on the ARCNET network that are configured to communicate with the repeater Faults regarding communication with repeater node identification address...

Page 57: ...Operation Language Group 1 2 3 OFF OFF OFF English English English OFF OFF ON Italian Lithuanian Lithuanian OFF ON OFF Dutch Belgium Polish Danish OFF ON ON Portuguese Hungarian Swedish ON OFF OFF Du...

Page 58: ...n 5 NEN Operation 6 EP Operation Lang Gr 1 Lang Gr2 Lang Gr 3 7 English English English 8 Italian Lithuanian Lithuanian 9 Dutch Belgium Polish Danish 10 Portuguese Hungarian Swedish 11 Dutch Holland C...

Page 59: ...lowed Not allowed Allowed 1 min time out Fire Brigade signal time out stopped by silence bell Fire Brigade Signal No No No Signal level 2 Stop No No No Stop level 2 Delay Allowed Allowed Allowed Allow...

Page 60: ...3252 6 2...

Reviews: