20
FP/FR
1100/
1200/2000 V6: Installation and Commissioning Manual
The total panel weight equals:
11 kg for size A cabinet (excluding batteries)
15 kg for size B cabinet (excluding batteries)
9 kg for size C cabinet (excluding batteries)
Figure 6:
Cable entries
CAUTION!
Mains wires (230V) must enter the cabinet from the left bottom hole in the
cabinet only.
Top entry violates EN60950 (IEC950) safety requirements and will
cause EMC
problems.
Mains wires must not be routed past the electronic modules in the rear of the panel. It
must be kept as short as possible and routed directly to the mains input connected to the
power supply (PS2000)