FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
11
Tamper switch (FP2000 Range only):
Fitted to the inside of the fire panel door to record any entry to the cabinet.
Third source (when implemented on the FP2000 range only):
Test button and LED to test total loss of power supply.
Communication ports:
•
2 x DB-9 serial port (set-up, upload/download, internal printer (where applicable),
graphics, remote operation/graphic package)
•
1 x current loop (to connect repeaters and fireman’s panels)
Current Loop:
•
Maximum 15 devices
•
Maximum 1 km between 2 current loop devices
•
Aritech FM800 / FR800 - German fire brigade panel (according to DIN 14661) can be
connected.
•
Cable capacitance max. 150 nF
3.2 Panel specifications
3.2.1
Standard Outputs
Standard Outputs
(All standard outputs are
located on the sounder
board.)
FP/FR1xxx & FR2000
(
FP1100 and FP1216 only;
FP1200 optional – SD1200
board used)
FP1216EN &
FP1264
(SD2000 board)
FP/FR2xxx
(FP2xxx only -
SD2000 board used)
OUT 1:
Output to alarm devices
(Sounders)
A: 24 V – 100 mA supervised*
(Supervision at 5V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680
output
OUT2:
Output to fire routing
equipment (Fire brigade)
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.8 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.8 A
supervised (Supervision
at 5V max.)
B: 3K3/680 Ohm
switched output
OUT3:
Output to fire protection
equipment
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
OUT4:
Output to fault warning
routings equipment
A: 24 V – 100 mA supervised*
(Supervision at 5 V max.)
B: 3K3/680 Ohm switched
output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output
A: 24 V - 0.1 A
supervised (Supervision
at 5 V max.)
B: 3K3/680 Ohm
switched output