FP/FR1100/1200/2000 V6: Installation and Commissioning Manual
17
CAUTION!
Mains wires (230 V) must enter the cabinet from the right bottom hole in the
cabinet only.
Top entry violates IEC950 safety requirements and will cause EMC
problems.
Mains wires must not be routed past the electronic modules in the rear of the panel. It
must be kept as short as possible and routed directly to the mains input.
4.1.3 Panel & repeater layout
Figure 3:
Panel layout
A.
FP1216EN &
FP1264
16. Host CPU board
B. FR1200 & FR2000
17. DB-9 port
1. Transformer
18. RS232 and current loop routing of wires
2. Battery link
19. ARCNET network card (top) (optional)
3. Battery terminal (+) (red)
20. Battery terminal (-) (black)
4. Mains terminal block
21. Battery and power supply connection terminals
5. Earth stud
22. Modem (MOD2000) power supply terminals
6. Main fuse and switch
23. Front-end processor board
7. Batteries 12V (2x) (optional)
24. Power supply board
8. Zone matrix display board (bottom) (optional)
25. Fault relay connections
9. Common LED board
26. Auxiliary power connections
10. Service commission mode select
27. Loop 1-4 terminal connections
11. Non-volatile memory lock
28. 2 Loop driver board
12. Memory back-up battery jumper
29. Sounder relay board
13. Numeric keypad
30. Modem (MOD2000) (optional)
14. LCD display
31. ARCNET network card (bottom) (NC2011)
15. Current loop terminals