14
FP/FR
1100/
1200/2000 V6: Installation and Commissioning Manual
3.2.4 Panel Operation
Battery operation - Normal operation
(No mains power)
FP12XX
FR1200/FR2000
FP1216EN &
FP1264
Current required by system
200 mA (max)
200 mA (max)
200 mA (max)
Loop current
- 2 loops
- 127 devices/loop @ 340 µA/device (DP951)
86 mA
0 mA
86 mA
Auxiliary current
0 mA
0 mA
0 mA
Total normal current
286 mA
200 mA
286 mA
Battery Operation - Alarm Operation
(No mains power)
FP12XX
FR1200/FR2000
FP1216EN &
FP1264
Normal current (as above)
286 mA (max)
200 mA (max)
286 mA (max)
Extra loop current (20 x LED @ 4 mA)
80 mA
0 mA
80 mA
Sounders (Sounder board: Outputs 1-4)
200 mA
0 mA
200 mA
Total alarm current
566 mA
200 mA
566 mA
Normal Operation
FP2416/2464 & FP2432/24128
FP2864, FP28255
Mains load (maximum)
200 VA
200 VA
Total output current (27.6 V)
4 A
4 A
Battery capacity I
AUX
= 0 (72H standby)
36 AH
58 AH
Battery capacity (maximum)
69 AH
69 AH
Required battery charging current
(Maximum battery capacity)
3.05 A
3.05 A
Current required by system (I
SYS
)*
0.5 A
0.8 A
Available auxiliary current
0.45 A
0.15 A
Alarm Operation
FP2416/2464 & FP2432/24128
FP2864, FP28255
Mains load (maximum)
200 VA
200 VA
Total output current (27.6 V)
4 A
4 A
Required battery charging current
(Maximum battery capacity)
0 A
0 A
Current required by system
0.6 A
1 A
Available auxiliary current
3.4 A
3 A
*I
SYS
calculated at 252 x 900 series ionisation detectors (FP2416/64)
1008 x 900 series ionisation detectors
(FP2864/255)
Charging current based to charge batteries up to 80% in 24 hours at 75% efficiency