Functions
INSYS GSM 4.3 I4
54
In order to
delete the assignments for additional recipients
, click onto the “de-
lete all connections” button.
In order to
establish a voice connection to a specified phone number
in case of
an alarm at the input, select on the “Alarm” tab for the respective alarm input
of the INSYS GSM 4.3 I4 “single alarm” in the drop-down list “alarm trigger”.
Select “voice” as
medium for the alarm transmission
via the drop-down list
“alarm transmission by”. Enter the phone number, to which the voice connec-
tion is to be established, into the entry field “recipient number”.
Configuration with AT commands
In order to
configure the behaviour of the IN-
SYS GSM 4.3 I4 in case of an alarm at the in-
puts
, use the command
Replace here
<in>
with the input number
<mode>
with the number of the action, where
the following is valid:
0 for no action (no dispatch)
1 for single SMS dispatch
2 for single message dispatch via data connec-
tion
3 for message output via data connection,
hang up after message dispatch
4 for pulse-based SMS dispatch
5 for the establishment of a voice connection
AT**INPUT<in>=<mode>
In order to
read out and store the phone num-
ber of the SMS Service Center from the SIM
card
, use the command
Please note that a capital “S” must be entered!
AT**SCN=S
In order to
enter the phone number of the
SMS Service Center
, use the command
Replace
<number>
with the phone number of
the SMS Service Center. If no number is en-
tered behind the “=”, the SMSC number will be
deleted.
AT**SCN=<number>