21
Code
Designation
Range
Factory
value
Modification
when motor
is ON
F1.35
Polarities reversal
of the DI1 to DI5
inputs (contacts
NO or NC)
Bit 1
Input DI1
High signal
0
00000
No
Low signal
1
Bit 10
Input DI2
High signal
0
Low signal
1
Bit 100
Input DI3
High signal
0
Low signal
1
Bit 1 000
Input DI4
High signal
0
Low signal
1
Bit 10 000
Input DI5
High signal
0
Low signal
1
F1.36
Polarities reversal
of the DI6 to DI10
inputs (contacts
NO or NC)
Bit 1
Input DI6
High signal
0
00000
No
Low signal
1
Bit 10
Input DI7
High signal
0
Low signal
1
Bit 100
Input DI8
High signal
0
Low signal
1
Bit 1 000
Input DI9
High signal
0
Low signal
1
Bit 10 000
Input DI10
High signal
0
Low signal
1
h.
Output settings
Code
Parameter
Setting range
Factory value
F2.02
Shift output signal 3
(TA1,TB1,TC1)
0 à 40
2
F2.04
Static output signal 1 (SPA)
0 à 40
1
Setting value
Function
Description
0
No output pilotage
No output pilotage
1
Inverter is ON
The output is active when the out put frequency is
different than zero.
2
Defect in inverter output
The output is active when the inverter stops due to
a defect