34
Low speed
48
About the setting defrosting time:
runtime
minute
Defrosting time
minute
Case 1
Runtime=45
10
Case 2
45
runtime 60
7.5
Case 3
60
runtime 90
8.5
Case 4
90
runtime 120
10
Case 5
120
runtime
12
2
AC will enter the defrosting mode if all of the following items are satisfied:
2.1 The compressor cumulative running time is over 45 minutes.
2.2 The compressor continuous running time is over 8 minutes.
2.3 The indoor fan is off or the indoor fan is running at breeze.
In this case, the defrosting time is ten minutes.
3
AC will enter the defrosting mode if all of the following items are satisfied:
3.1 AC has no defrost before.
3.2 The cumulative compressor running time is over 45 minutes.
3.3 The indoor fan has been run at low speed over 2 minutes.
3.4 The 1.2 and 1.3 are satisfied.
In this case, the defrosting time is ten minutes.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
(1) The defrosting time is reached to the setting value.
(2) The defrosting has been running for 3 minutes and T2
2
.
(3)
The defrosting has been running for 2 minutes, check the value of T2. If T2
-
T2
min
2
during 4
minutes, the defrosting will terminate.
Defrosting action
Summary of Contents for EV10C2DB6
Page 11: ...9 Model R mm L mm H mm Dimension of installation hole mm EV24C2DB6 163 293 45 65 H L R ...
Page 15: ...13 5 Wiring Diagram 5 1 Indoor Units EV10C2DB6 EV13C2DB6 EV18C2DB6 ...
Page 16: ...14 EV24C2DB6 ...
Page 17: ...15 5 2 Outdoor Units H10C2MR63 H13C2MR63 H18C2MR63 ...
Page 18: ...16 H24C2MR63 ...
Page 41: ...39 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed out of control diagnosis and solution ...
Page 43: ...41 9 2 5 Indoor outdoor unit s communication error diagnosis and solution ...
Page 44: ...42 9 2 6 Refrigerant leakage detection diagnosis and solution 0 1 ...