33
Auto fan action:
When T1-Ts>2
, the indoor fan will run at low speed.
When T1-Ts 0
, the indoor fan will run at medium speed.
8.4.3.4 Defrosting mode
Condition of defrosting:
1
AC will enter the defrosting mode if all of the following items are satisfied.
1.1 After the compressor keeps running 8 minutes, T max
T 4
T=T2-T1
T = T, if the indoor fan=low speed.
T = T+3, if the indoor fan=medium speed.
T = T+5, if the indoor fan=high speed.
1.2 AC meets A1 or A2.
A1: The cumulative compressor running time is between 45~120 minutes. Meanwhile the value of
T
meets the below table.
T
High speed
TH
DEFROST
Medium speed
TM
DEFROST
Low speed
TL
DEFROST
A2: The cumulative compressor running time is over 120 minutes. Meanwhile the value of
T meets
the below table.
T
High speed
TH
DEFROST
+2
Medium speed
TM
DEFROST
+2
Low speed
TL
DEFROST
+2
1.3 If the fan speed and the evaporator coil temp.T2 meet one of the below issue:
T2
High speed
43
Medium speed
46
Summary of Contents for EV10C2DB6
Page 11: ...9 Model R mm L mm H mm Dimension of installation hole mm EV24C2DB6 163 293 45 65 H L R ...
Page 15: ...13 5 Wiring Diagram 5 1 Indoor Units EV10C2DB6 EV13C2DB6 EV18C2DB6 ...
Page 16: ...14 EV24C2DB6 ...
Page 17: ...15 5 2 Outdoor Units H10C2MR63 H13C2MR63 H18C2MR63 ...
Page 18: ...16 H24C2MR63 ...
Page 41: ...39 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed out of control diagnosis and solution ...
Page 43: ...41 9 2 5 Indoor outdoor unit s communication error diagnosis and solution ...
Page 44: ...42 9 2 6 Refrigerant leakage detection diagnosis and solution 0 1 ...