17
6. Installation details
6.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional
tightening torque
mm
inch
N.cm
N.cm
6.35
1/4
1500
(153kgf.cm)
1600
(163kgf.cm)
9.52
3/8
2500
(255kgf.cm)
2600
(265kgf.cm)
12.7
1/2
3500
(357kgf.cm)
3600
(367kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and 6
0.75
>6 and 10
1.0
>10 and 16
1.5
>16 and 25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before
selecting the cable, fuse and switch.
Summary of Contents for EV10C2DB6
Page 11: ...9 Model R mm L mm H mm Dimension of installation hole mm EV24C2DB6 163 293 45 65 H L R ...
Page 15: ...13 5 Wiring Diagram 5 1 Indoor Units EV10C2DB6 EV13C2DB6 EV18C2DB6 ...
Page 16: ...14 EV24C2DB6 ...
Page 17: ...15 5 2 Outdoor Units H10C2MR63 H13C2MR63 H18C2MR63 ...
Page 18: ...16 H24C2MR63 ...
Page 41: ...39 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed out of control diagnosis and solution ...
Page 43: ...41 9 2 5 Indoor outdoor unit s communication error diagnosis and solution ...
Page 44: ...42 9 2 6 Refrigerant leakage detection diagnosis and solution 0 1 ...