32
8.4.3 Heating Mode (For Heating & Cooling model)
8.4.3.1 Compressor running rules:
When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is
lower than Tk, the compressor and outdoor fan will start up.
While Tj=Ts; T
k
=Ts-2 for
models. Tj=Ts+4;T
k
=Ts+2 for other models.
8.4.3.2 Outdoor fan running rules:
The outdoor units have single fan speed. The outdoor fan will run following the compressor except
when AC is in evaporator high temp. protection in heating mode , condenser high temp. protection in
cooling mode ,defrosting mode and the current protection.
8.4.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind
function has the priority.
Anti-cold wind function:
TE2
TE3
TE2-6
TE1
T2
TE3-6
Setting
Low
Breeze
Off
TE1-6