Innova Air Compact 4M Instruction Manual Download Page 20

Instruction manual 

Pag. 20 of 28 

Date 2021-07-27 

 

 

 

 

6.1.1 ALARMS and  troubleshooting  

 

In case of failure the following codes are shown on two digits display in the electrical box:  
E1

Room temperature: sensor failure; 

E2

Evaporator coil temperature: sensor failure;  

E3

: 

Seawater inlet temperature: sensor failure;  

E4

Condenser temperature: sensor failure;  

E5

: 

Indoor DC Fan failure; 

E7: Communication error between main MCU and room thermostat;  

LP: Low Pressure switch alarm; HP: High Pressure switch alarm; 

LT: low evaporator temperature in heating mode 

 

In  case  of  alarm  from  E1  to  E7  please  try  to  switch  OFF  the  unit  and  then  ON  again,  if  the  problem  persists  call  a 
INNOVA authorized service. 

 

The  HP  alarm  in  cooling  mode  could  be  due  to  a  clogged  source  circuit,  or  the  pump  not  working  properly  (e.g. 
thermal load protection). Please visually check the overboard drain, and in case of poor water flow, check and clean 
all parts involved. 

 

In case of HP alarm appears in heating mode, the air flow through the air outlet could be too low. Please check all the 
ducts are not obstructed somewhere. Also, the air suction filter, if dirty, could  cause high pressure, provide then    to 
clean it before restarting the unit. 

 

LP alarm is most commonly due to a consistent leakage of refrigerant, check the refrigerating circuit for leakages. 

 

In  case  of  LT  alarm,  the  problem  may  be  due  to  poor  water  circulation  on  the  source  side  or  too  low  water 
temperature (below 5°C). Please check the seawater flow first as specified above. 

 

7.0

 

WORKING LIMITS 

The unit operates correctly within the following ranges: 

 

Summer cooling mode: 15°C < source-side temperature< 40°C 

 

Winter heating mode: 10°C < source-side temperature < 20°C 

Should working conditions be out of these ranges, in your particular application, please contact INNOVA 

before installation in order to find a suitable solution. 

 

7.1 

Recommendations for sources with sea, lake or river water 

Localized situations: in some regions, it is common to experience a tremendous presence of jellyfish or 
seaweed concentrated in back bay marinas for some periods of time. This can clog strainers, water pumps 
and heat exchangers in a little while, causing shut-down faults and sometimes equipment damage. In such 
particular conditions, please seek for the advice of a local INNOVA service representative. Any possible 
modification to the overall system (self-contained, pumps, strainers, etc.) that could overtake the problem 
must be approved by INNOVA, otherwise warranty coverage will expire. 

 

The standard pump is not self-priming: any damage incurred due to a pump running dry is not covered 
under warranty. Air conditioning system must be switched off, as well as pumps, whenever there is a risk of 
pump loosing priming, due to particular seawater conditions related to the boat type and its speed. The 
compressor could be damaged if the seawater flow through the heat exchanger is considerably reduced. 

 
 

Summary of Contents for Air Compact 4M

Page 1: ...Via I Maggio 8 38089 STORO TN Italia Tel 39 0465 670104 Web site www innovaenergie com eMail info innovaenergie com WATER TO AIR S E L F C O N T AI NED UNITS DC INVERTER Technology Air Compact 4M Air...

Page 2: ...4 1 1 SAFETY MEASURES 7 4 1 2 PROHIBITIONS 7 4 1 3 RESPONSIBILITY 8 5 0 INSTALLATION 8 5 1 1 HYDRAULIC CONNECTIONS 10 5 1 2 AIR DUCTS CONNECTION 13 5 1 3 ELECTRICAL CONNECTION 16 5 1 4 THERMOSTAT BULB...

Page 3: ...en prepared with the aim to give you all the explanations to be able to properly install the unit SELF CONTAINED Air Compact and to better manage the device Improper installation procedures can result...

Page 4: ...ING Lift the unit avoiding to catch it in sensitive parts such as tubing and air adapters When the load is lifted off the ground stay away from below and surrounding area During transport operations r...

Page 5: ...temperature and relative humidity fluctuations By using unit INVERTER Brushless DC it is possible install on board a smaller power generator than the one necessary for operating a traditional ON OFF a...

Page 6: ...rmal load and it allows to keep the air temperature stable always near the Set Point value w ithout sharp fluctuations Thanks to the Brushless DC motor and to the sound absorbing insulation silence is...

Page 7: ...evices The installation and maintenance of air conditioning equipment may be dangerous because within these devices there are pressurized refrigerant gas and electrical devices Therefore the installat...

Page 8: ...the mains by putting the system power switch to OFF position Do not dispose abandon or leave within the reach of children the packaging material because it can be a potential source of danger It is fo...

Page 9: ...ion of the appliance raise the manufacturer from any form of guarantee and liability for damage caused to people animals or things WARNING The appliance must be installed in a protected area and in su...

Page 10: ...1 HY DRAUL I C CO NNE CT I O NS The following is a summary of how to install the unit on a source circuit and at the outlet CORRECT SYSTEM INSTALLATION The minimum nominal diameter of the connecting p...

Page 11: ...21 07 27 SOURCE CIRCUIT Installing electric pump The source side pump is needed to circulate the amount of water required in the heat exchanger If necessary the system can also work in a closed circui...

Page 12: ...operations it is essential that each hydraulic connection is provided with the respective shut off valve DRAIN 5 1 2 AI R DUCT S CO NNE CT I O N IMPORTANT Both outlet fittings can be ducted allowing t...

Page 13: ...at its maximum performance with one duct only using the size 150mm to do that the horizontal 125 mm flange must be dismounted and substituted with the 150mm flange supplied with the unit The top outle...

Page 14: ...uction area of the unit Air distribution The system needs a correct air flow in order to work efficiently It is therefore important to get the correct distribution without bottlenecks by maintaining t...

Page 15: ...environment through an air gas exchanger equipped with aluminum fins having small pitch A filter must be located upstream the exchanger in order to protect it from dust NOTE the filter must be easy re...

Page 16: ...les respecting the data provided in chapter Technical data and it shall be properly grounded FIXING The electrical box is delivered fixed on the self contained unit however in case of limited space du...

Page 17: ...te 2021 07 27 5 1 4 TH E R M O S TA T BUL BS A temperature sensor bulb is fixed to the drain pan through a bracket and located near the unit air suction The main temperature sensor working sensor is l...

Page 18: ...thermostat must be installed in a proper position away from direct heat source The set point temperature and real value are shown on the thermostat display display 6 a liu c n 1o fi i i a lr e f Jl _...

Page 19: ...Instruction manual Pag 19 of 28 Date 2021 07 27...

Page 20: ...due to poor water circulation on the source side or too low water temperature below 5 C Please check the seawater flow first as specified above 7 0 WORKING LIMITS The unit operates correctly within th...

Page 21: ...ons could lead to an abnormal operating condition that could cause injury or damage to any equipment or other property additional precautions must be designed into the control system Other devices lim...

Page 22: ...end customer Transportation damages This should be claimed directly with the forwarding company Repair costs due to failure of INNOVA equipment due to negligence improper installation or non respectin...

Page 23: ...ler Refers to pages containing instructions or information for the installer S Service for the CUSTOMER TECHNICAL ASSISTANCE SERVICE installer Safety pictograms Warning The operation described may cau...

Page 24: ...1 11 6 Activation 11 11 7 Heating air conditioning mode setting 11 11 8 Stand by 11 11 9 Temperature selection 11 11 10 Automatic operation 12 11 11 Medium speed fan operation 12 11 12 Minimum fan spe...

Page 25: ...ode 11 2 Display 11 1 Electronic smart touch panel with room probe Touch control panel is an electronic thermostat with a room temperature probe for controlling air conditioning units both On Off and...

Page 26: ...Instruction manual Pag 25 of 28 Date 2021 07 27...

Page 27: ...N Stand by key From off to on Select one of the 4 operating modes by pressing the relative key Key Operation Display Keep the Heating Cooling key pressed for approx 2 seconds to change the mode betwee...

Page 28: ...other degree after two hours in cooling mode Key Operation Display Press and hold the Max Operation key The function being activated is indicated by the relevant symbol appearing on thedisplay In this...

Page 29: ...justed in a range from 9 to 12 K in intervals of 0 1 C Use this adjustment with care and only after having actually detected a discrepancy compared with the actual room temperature using a reliabledev...

Page 30: ..._____ _ _____ _ _____ _ _ _____ _ _____ _ _____ _ _____ _ _____ _ _____ _ _____ _ _ _____ _ _____ _ _____ _ _____ _ _____ _ _____ _ _____ _ _ _____ _ _____ _ _____ _ _____ _ Date 2018 11 27 Instructio...

Reviews: