MAXIM Installation Instructions
© Mass Electronics Pty Ltd 2011
Chapter 3 – Electrical Installation
3-3.1.2 Universal Inputs
The MAXIM I, II, III, and 1010 controllers are equipped with Universal Inputs that can be configured to
suit a wide range of applications as described in Table 3-3 below. Each Universal Input has a signal
terminal (+) and a reference terminal (–).
Table 3-3:
Input/Output Range for Universal Inputs
Input Type
Input Range
Output Range
Analogue
0-10VDC
0-10VDC
Thermistor
High Thermistor 100kΩ – 680kΩ
-20°C to 100°C
Low Thermistor 662kΩ – 12kΩ
-50°C to 20°C
Lux Sensor
1MΩ – 0Ω
3 to 2500 LUX
Digital
Voltage
0 – 10VDC
OFF or ON
Contact
Open or Closed
OFF or ON
Pulse Counter
Voltage
0 – 10V Square Wave
20ms Min. ON Time
20ms Min. OFF Time
0 to 25 pulses per second
Contact
Open or Closed
20ms Min. ON Time
20ms Min. OFF Time
0 to 25 pulses per second
Duty Cycle
Voltage
0 – 1 Square Wave
1 – 13Hz
0 to 100%
Contact
Open or Closed
1 – 13Hz
0 to 100%
Please note that the LUX Sensor input mode is suitable for switching based on ambient light levels, but is NOT
suitable for any operation which requires the accurate measurement or recording of light levels.
NOTE
Summary of Contents for MAXIM 1010
Page 1: ...MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 9: ...Chapter 1 Preliminary Information MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 15: ...MAXIM Series Controllers INSTALLATION INSTRUCTIONS Chapter 2 Mechanical Installation...
Page 23: ...Chapter 3 Electrical Installation MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 41: ...Chapter 4 Network Installation MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 43: ...Chapter 5 Commissioning MAXIM Series Controllers INSTALLATION INSTRUCTIONS...