3-3.2.3 TRIAC Outputs
The MiniMAX controllers are equipped with four TRIAC outputs used for switching the 24VAC power
supply through to the outputs of the controller. There are four 24V terminals for each TRIAC output,
and two 0V terminals that are shared by the four TRIAC outputs. The TRIAC outputs are rated at
a minimum current of 20 m A and maximum current of 250 m A. The TRIAC outputs can operate in
two modes: Pulse Width Modulation (PWM) or Digital (ON/OFF). The output range for both modes of
operation are described in Table 3-8 below.
3-3.3 VAVMax and MicroMAX Controllers
This section of the manual provides wiring information for the VAVMax and MicroMAX controllers.
Information is provided on wiring a power source and all associated inputs and outputs.
The general layout of the input and output terminals for each of these controllers is illustrated in
Figure 3-8 below.
Table 3-8:
MiniMAX Controllers: Modes of Operation for TRIAC Outputs
TRIAC Output Mode
Output Range
Digital
ON or OFF
PWM Output
0-100% (0-10VDC)
Figure 3-8:
VAVMax and MicroMAX Controller Terminal Connection Layout
Summary of Contents for MAXIM 1010
Page 1: ...MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 9: ...Chapter 1 Preliminary Information MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 15: ...MAXIM Series Controllers INSTALLATION INSTRUCTIONS Chapter 2 Mechanical Installation...
Page 23: ...Chapter 3 Electrical Installation MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 41: ...Chapter 4 Network Installation MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Page 43: ...Chapter 5 Commissioning MAXIM Series Controllers INSTALLATION INSTRUCTIONS...